DKSF-70-3-X-X-1

File: DKSF-70-3-X-X-1.mib (23098 bytes)

Imported modules

SNMPv2-SMI SNMPv2-TC SNMPv2-MIB

Imported symbols

enterprises MODULE-IDENTITY OBJECT-TYPE
Counter32 Gauge32 Counter64
Integer32 TimeTicks NOTIFICATION-TYPE
TEXTUAL-CONVENTION DisplayString TruthValue
TimeStamp snmpTraps

Defined Types

NpRelayEntry  
SEQUENCE    
  npRelayN INTEGER
  npRelayMode INTEGER
  npRelayStartReset INTEGER
  npRelayMemo DisplayString
  npRelayState INTEGER

NpThermoEntry  
SEQUENCE    
  npThermoSensorN INTEGER
  npThermoValue INTEGER
  npThermoStatus INTEGER
  npThermoLow INTEGER
  npThermoHigh INTEGER
  npThermoMemo DisplayString

NpIoEntry  
SEQUENCE    
  npIoLineN INTEGER
  npIoLevelIn INTEGER
  npIoLevelOut INTEGER
  npIoMemo DisplayString
  npIoPulseCounter Counter32
  npIoSinglePulseDuration INTEGER
  npIoSinglePulseStart INTEGER

NpCurLoopEntry  
SEQUENCE    
  npCurLoopN INTEGER
  npCurLoopStatus INTEGER
  npCurLoopI INTEGER
  npCurLoopV INTEGER
  npCurLoopR INTEGER
  npCurLoopPower INTEGER

Defined Values

uniPingServerSolutionV3 1.3.6.1.4.1.25728.70
Generic MIB for NetPing remote sensing and control
MODULE-IDENTITY    

lightcom 1.3.6.1.4.1.25728
OBJECT IDENTIFIER    

npTrapInfo 1.3.6.1.4.1.25728.90
OBJECT IDENTIFIER    

npTrapEmailTo 1.3.6.1.4.1.25728.90.1
user-specified e-mail for NetPing Trap Forwarding Service
OBJECT-TYPE    
  DisplayString  

npRelay 1.3.6.1.4.1.25728.5500
OBJECT IDENTIFIER    

npRelayTable 1.3.6.1.4.1.25728.5500.5
Watchdog and outlet/relay control table
OBJECT-TYPE    
  SEQUENCE OF  
    NpRelayEntry

npRelayEntry 1.3.6.1.4.1.25728.5500.5.1
Relay/outlet table row
OBJECT-TYPE    
  NpRelayEntry  

npRelayN 1.3.6.1.4.1.25728.5500.5.1.1
The N of output relay
OBJECT-TYPE    
  INTEGER 1..1  

npRelayMode 1.3.6.1.4.1.25728.5500.5.1.2
Control of relay: -1 - flip, works only for manual On and Off state 0 - manual off 1 - manual on 4 - logic
OBJECT-TYPE    
  INTEGER flip(-1), off(0), on(1), logic(4)  

npRelayStartReset 1.3.6.1.4.1.25728.5500.5.1.3
Write 1 to start reset (switch relay off for some time)
OBJECT-TYPE    
  INTEGER  

npRelayMemo 1.3.6.1.4.1.25728.5500.5.1.6
Relay memo
OBJECT-TYPE    
  DisplayString  

npRelayState 1.3.6.1.4.1.25728.5500.5.1.15
Actual relay state at the moment, regardless of source of control. 0 - relay is off 1 - relay is on
OBJECT-TYPE    
  INTEGER off(0), on(1)  

npThermo 1.3.6.1.4.1.25728.8800
OBJECT IDENTIFIER    

npThermoTable 1.3.6.1.4.1.25728.8800.1
Thermo Sensors Table
OBJECT-TYPE    
  SEQUENCE OF  
    NpThermoEntry

npThermoEntry 1.3.6.1.4.1.25728.8800.1.1
Thermo Sensors Table Row
OBJECT-TYPE    
  NpThermoEntry  

npThermoSensorN 1.3.6.1.4.1.25728.8800.1.1.1
The id of temperature sensor, 1 to 8
OBJECT-TYPE    
  INTEGER 1..8  

npThermoValue 1.3.6.1.4.1.25728.8800.1.1.2
Temperature, deg.C
OBJECT-TYPE    
  INTEGER -60..280  

npThermoStatus 1.3.6.1.4.1.25728.8800.1.1.3
Temperature status (0=fault, 1=underheat, 2=normal, 3=overheat)
OBJECT-TYPE    
  INTEGER failed(0), low(1), norm(2), high(3)  

npThermoLow 1.3.6.1.4.1.25728.8800.1.1.4
Bottom margin of normal temperature range, deg.C
OBJECT-TYPE    
  INTEGER -60..280  

npThermoHigh 1.3.6.1.4.1.25728.8800.1.1.5
Top margin of normal temperature range, deg.C
OBJECT-TYPE    
  INTEGER -60..280  

npThermoMemo 1.3.6.1.4.1.25728.8800.1.1.6
T channel memo
OBJECT-TYPE    
  DisplayString  

npThermoTraps 1.3.6.1.4.1.25728.8800.2
OBJECT IDENTIFIER    

npThermoTrapPrefix 1.3.6.1.4.1.25728.8800.2.0
OBJECT IDENTIFIER    

npThermoTrapSensorN 1.3.6.1.4.1.25728.8800.2.1
The id of temperature sensor, 1 to 8
OBJECT-TYPE    
  INTEGER 1..8  

npThermoTrapValue 1.3.6.1.4.1.25728.8800.2.2
Temperature, deg.C
OBJECT-TYPE    
  INTEGER -60..280  

npThermoTrapStatus 1.3.6.1.4.1.25728.8800.2.3
Temperature status (0=fault, 1=underheat, 2=normal, 3=overheat)
OBJECT-TYPE    
  INTEGER failed(0), low(1), norm(2), high(3)  

npThermoTrapLow 1.3.6.1.4.1.25728.8800.2.4
Bottom margin of normal temperature range, deg.C
OBJECT-TYPE    
  INTEGER -60..280  

npThermoTrapHigh 1.3.6.1.4.1.25728.8800.2.5
Top margin of normal temperature range, deg.C
OBJECT-TYPE    
  INTEGER -60..280  

npThermoTrapMemo 1.3.6.1.4.1.25728.8800.2.6
T channel memo
OBJECT-TYPE    
  DisplayString  

npThermoTrap 1.3.6.1.4.1.25728.8800.2.0.1
Status of Thermo sensor is changed (crossing of normal temp. range)
NOTIFICATION-TYPE    

npIo 1.3.6.1.4.1.25728.8900
OBJECT IDENTIFIER    

npIoTable 1.3.6.1.4.1.25728.8900.1
Digital Input/output Table
OBJECT-TYPE    
  SEQUENCE OF  
    NpIoEntry

npIoEntry 1.3.6.1.4.1.25728.8900.1.1
Digital Input/output Table Row
OBJECT-TYPE    
  NpIoEntry  

npIoLineN 1.3.6.1.4.1.25728.8900.1.1.1
Number of IO line, from 1 to max supported
OBJECT-TYPE    
  INTEGER 1..8  

npIoLevelIn 1.3.6.1.4.1.25728.8900.1.1.2
Input level, 0 or 1
OBJECT-TYPE    
  INTEGER 0..1  

npIoLevelOut 1.3.6.1.4.1.25728.8900.1.1.3
Output level, 0 or 1
OBJECT-TYPE    
  INTEGER 0..1  

npIoMemo 1.3.6.1.4.1.25728.8900.1.1.6
IO line memo
OBJECT-TYPE    
  DisplayString  

npIoPulseCounter 1.3.6.1.4.1.25728.8900.1.1.9
Pulse Counter on IO input line (counts positive fronts) Write 0 to reset.
OBJECT-TYPE    
  Counter32  

npIoSinglePulseDuration 1.3.6.1.4.1.25728.8900.1.1.12
Set duration of single pulse on IO output line, 100ms to 25500ms, min. step is 100ms
OBJECT-TYPE    
  INTEGER 100..25500  

npIoSinglePulseStart 1.3.6.1.4.1.25728.8900.1.1.13
Write 1 to start single pulse on IO output. Output will be inverted for time, specified by npIoSinglePulseDuration
OBJECT-TYPE    
  INTEGER  

npIoTraps 1.3.6.1.4.1.25728.8900.2
OBJECT IDENTIFIER    

npIoTrapPrefix 1.3.6.1.4.1.25728.8900.2.0
OBJECT IDENTIFIER    

npIoTrapLineN 1.3.6.1.4.1.25728.8900.2.1
Trap data, Number of IO line
OBJECT-TYPE    
  INTEGER 1..2  

npIoTrapLevelIn 1.3.6.1.4.1.25728.8900.2.2
Trap data, new Input level, 0 or 1
OBJECT-TYPE    
  INTEGER 0..1  

npIoTrapMemo 1.3.6.1.4.1.25728.8900.2.6
Trap data, IO line memo
OBJECT-TYPE    
  DisplayString  

npIoTrap 1.3.6.1.4.1.25728.8900.2.0.1
Input state of IO line is changed
NOTIFICATION-TYPE    

npCurLoop 1.3.6.1.4.1.25728.8300
OBJECT IDENTIFIER    

npCurLoopTable 1.3.6.1.4.1.25728.8300.1
Current loop sensors Table
OBJECT-TYPE    
  SEQUENCE OF  
    NpCurLoopEntry

npCurLoopEntry 1.3.6.1.4.1.25728.8300.1.1
Current loop sensors Table Row
OBJECT-TYPE    
  NpCurLoopEntry  

npCurLoopN 1.3.6.1.4.1.25728.8300.1.1.1
Index of current loop, 1 to max supported
OBJECT-TYPE    
  INTEGER 1..8  

npCurLoopStatus 1.3.6.1.4.1.25728.8300.1.1.2
Status of the loop 0=Normal, 1=Alert, 2=Cut, 3=Short, 4=Not Powered
OBJECT-TYPE    
  INTEGER ok(0), alert(1), cut(2), short(3), notPowered(4)  

npCurLoopI 1.3.6.1.4.1.25728.8300.1.1.3
Loop current, mA
OBJECT-TYPE    
  INTEGER 0..99999  

npCurLoopV 1.3.6.1.4.1.25728.8300.1.1.4
Voltage drop on the loop, mV
OBJECT-TYPE    
  INTEGER 0..99999  

npCurLoopR 1.3.6.1.4.1.25728.8300.1.1.5
Resistance of the loop, Ohm
OBJECT-TYPE    
  INTEGER 0..99999  

npCurLoopPower 1.3.6.1.4.1.25728.8300.1.1.7
Control of loop power 0=Off, 1=On, 2=reset by off/on power
OBJECT-TYPE    
  INTEGER off(0), on(1), cyclePower(2)  

npCurLoopTraps 1.3.6.1.4.1.25728.8300.2
OBJECT IDENTIFIER    

npCurLoopTrapPrefix 1.3.6.1.4.1.25728.8300.2.0
OBJECT IDENTIFIER    

npCurLoopTrapN 1.3.6.1.4.1.25728.8300.2.1
Index of current loop, which status has changed
OBJECT-TYPE    
  INTEGER 1..8  

npCurLoopTrapStatus 1.3.6.1.4.1.25728.8300.2.2
Status of the loop 0=Normal, 1=Alert, 2=Cut, 3=Short, 4=Not Powered
OBJECT-TYPE    
  INTEGER ok(0), alert(1), cut(2), short(3), notPowered(4)  

npCurLoopTrapI 1.3.6.1.4.1.25728.8300.2.3
Loop current, mA
OBJECT-TYPE    
  INTEGER 0..99999  

npCurLoopTrapV 1.3.6.1.4.1.25728.8300.2.4
Voltage drop on the loop, mV
OBJECT-TYPE    
  INTEGER 0..99999  

npCurLoopTrapR 1.3.6.1.4.1.25728.8300.2.5
Resistance of the loop, Ohm
OBJECT-TYPE    
  INTEGER 0..99999  

npCurLoopTrapPower 1.3.6.1.4.1.25728.8300.2.7
Status of loop power 0=Off, 1=On
OBJECT-TYPE    
  INTEGER off(0), on(1)  

npCurLoopTrap 1.3.6.1.4.1.25728.8300.2.0.1
Status of current loop N has changed!
NOTIFICATION-TYPE    

npRelHumidity 1.3.6.1.4.1.25728.8400
OBJECT IDENTIFIER    

npRelHumSensor 1.3.6.1.4.1.25728.8400.2
OBJECT IDENTIFIER    

npRelHumSensorStatus 1.3.6.1.4.1.25728.8400.2.3
Status of the Rel.Humidity Sensor One 1=Normal, 0=Error or Sensor isn't connected
OBJECT-TYPE    
  INTEGER error(0), ok(1)  

npRelHumSensorValueH 1.3.6.1.4.1.25728.8400.2.2
Relative humidity value, %
OBJECT-TYPE    
  INTEGER 0..100  

npRelHumSensorValueT 1.3.6.1.4.1.25728.8400.2.4
Sensor temperature, deg.C
OBJECT-TYPE    
  INTEGER -60..200  

npRelHumSensorStatusH 1.3.6.1.4.1.25728.8400.2.5
Status of Relative Humiduty
OBJECT-TYPE    
  INTEGER sensorFailed(0), belowSafeRange(1), inSafeRange(2), aboveSafeRange(3)  

npRelHumSafeRangeHigh 1.3.6.1.4.1.25728.8400.2.7
Relative Humidity safe range, top margin, %RH
OBJECT-TYPE    
  INTEGER 0..100  

npRelHumSafeRangeLow 1.3.6.1.4.1.25728.8400.2.8
Relative Humidity safe range, bottom margin, %RH
OBJECT-TYPE    
  INTEGER 0..100  

npRelHumSensorValueT100 1.3.6.1.4.1.25728.8400.2.9
Sensor temperature, deg.C * 100 (fixed point two decimal places) Used to get access to the fractional part of T value
OBJECT-TYPE    
  Integer32  

npRelHumTraps 1.3.6.1.4.1.25728.8400.9
OBJECT IDENTIFIER    

npRelHumTrapPrefix 1.3.6.1.4.1.25728.8400.9.0
OBJECT IDENTIFIER    

npRelHumTrap 1.3.6.1.4.1.25728.8400.9.0.1
Status of Relative Humidity RH sensor has changed!
NOTIFICATION-TYPE    

npGsm 1.3.6.1.4.1.25728.3800
OBJECT IDENTIFIER    

npGsmInfo 1.3.6.1.4.1.25728.3800.1
OBJECT IDENTIFIER    

npGsmFailed 1.3.6.1.4.1.25728.3800.1.1
Firmware's GSM module status
OBJECT-TYPE    
  INTEGER ok(0), failed(1), fatalError(2)  

npGsmRegistration 1.3.6.1.4.1.25728.3800.1.2
Status of modem registration in GSM network (AT+CREG? result)
OBJECT-TYPE    
  INTEGER impossible(0), homeNetwork(1), searching(2), denied(3), unknown(4), roaming(5), infoUpdate(255)  

npGsmStrength 1.3.6.1.4.1.25728.3800.1.3
GSM signal strength. 0..31 = 0..100%, 99 = unknown or n/a, 255 = updating info
OBJECT-TYPE    
  INTEGER 0..255  

npGsmTraps 1.3.6.1.4.1.25728.3800.2
OBJECT IDENTIFIER    

npGsmTrapPrefix 1.3.6.1.4.1.25728.3800.2.0
OBJECT IDENTIFIER    

npGsmTrap 1.3.6.1.4.1.25728.3800.2.0.1
GSM modem or SMS firmware problems
NOTIFICATION-TYPE    

npIr 1.3.6.1.4.1.25728.7900
OBJECT IDENTIFIER    

npIrCtrl 1.3.6.1.4.1.25728.7900.1
OBJECT IDENTIFIER    

npIrPlayCmd 1.3.6.1.4.1.25728.7900.1.1
Write IR command number to send IR command
OBJECT-TYPE    
  INTEGER 1..16  

npIrReset 1.3.6.1.4.1.25728.7900.1.2
Write 1 to reset IR transiever. After reset, send IR command and check npIrStatus.
OBJECT-TYPE    
  INTEGER 0..1  

npIrStatus 1.3.6.1.4.1.25728.7900.1.3
IR transiever status
OBJECT-TYPE    
  INTEGER ok(0), busyCaptureWaitingButton(1), busyCaptureWaitingIr(2), busyPlayback(3), error(255)  

npReboot 1.3.6.1.4.1.25728.911
OBJECT IDENTIFIER    

npSoftReboot 1.3.6.1.4.1.25728.911.1
Write 1 to reboot device after current operations completition
OBJECT-TYPE    
  INTEGER  

npResetStack 1.3.6.1.4.1.25728.911.2
Write 1 to re-initialize network stack
OBJECT-TYPE    
  INTEGER  

npForcedReboot 1.3.6.1.4.1.25728.911.3
Write 1 to immediate forced reboot
OBJECT-TYPE    
  INTEGER