CPQCMC-MIB

File: CPQCMC-MIB.mib (103759 bytes)

Imported modules

CPQHOST-MIB RFC1213-MIB RFC-1212
RFC-1215

Imported symbols

compaq DisplayString OBJECT-TYPE
sysName sysContact sysLocation
sysDescr TRAP-TYPE

Defined Types

CpqCmcTrapEntry  
SEQUENCE    
  cpqCmcTrapIndex INTEGER
  cpqCmcTrapStatus INTEGER
  cpqCmcTrapIPaddress DisplayString

CpqCmcLogEntry  
SEQUENCE    
  cpqCmcLogIndex INTEGER
  cpqCmcLogDate DisplayString
  cpqCmcLogTime DisplayString
  cpqCmcLogText DisplayString
  cpqCmcLogClass DisplayString

Defined Values

cpqCmc 1.3.6.1.4.1.232.153
OBJECT IDENTIFIER    

cpqCmcMibRev 1.3.6.1.4.1.232.153.1
OBJECT IDENTIFIER    

cpqCmcComponent 1.3.6.1.4.1.232.153.2
OBJECT IDENTIFIER    

cpqCmcInterface 1.3.6.1.4.1.232.153.2.1
OBJECT IDENTIFIER    

cpqCmcOsCommon 1.3.6.1.4.1.232.153.2.1.1
OBJECT IDENTIFIER    

cpqCmcDevice 1.3.6.1.4.1.232.153.2.2
OBJECT IDENTIFIER    

cpqCmcSetup 1.3.6.1.4.1.232.153.2.2.2
OBJECT IDENTIFIER    

cpqCmcSetupConfig 1.3.6.1.4.1.232.153.2.2.2.1
OBJECT IDENTIFIER    

cpqCmcSetupGeneral 1.3.6.1.4.1.232.153.2.2.2.1.1
OBJECT IDENTIFIER    

cpqCmcSetupEvents 1.3.6.1.4.1.232.153.2.2.2.1.2
OBJECT IDENTIFIER    

cpqCmcSetupTemp1 1.3.6.1.4.1.232.153.2.2.2.1.2.1
OBJECT IDENTIFIER    

cpqCmcSetupTemp2 1.3.6.1.4.1.232.153.2.2.2.1.2.2
OBJECT IDENTIFIER    

cpqCmcSetupFan1 1.3.6.1.4.1.232.153.2.2.2.1.2.3
OBJECT IDENTIFIER    

cpqCmcSetupFan2 1.3.6.1.4.1.232.153.2.2.2.1.2.4
OBJECT IDENTIFIER    

cpqCmcSetupVoltage 1.3.6.1.4.1.232.153.2.2.2.1.2.5
OBJECT IDENTIFIER    

cpqCmcSetupHumidity 1.3.6.1.4.1.232.153.2.2.2.1.2.6
OBJECT IDENTIFIER    

cpqCmcSetupInput1 1.3.6.1.4.1.232.153.2.2.2.1.2.7
OBJECT IDENTIFIER    

cpqCmcSetupInput2 1.3.6.1.4.1.232.153.2.2.2.1.2.8
OBJECT IDENTIFIER    

cpqCmcSetupInput3 1.3.6.1.4.1.232.153.2.2.2.1.2.9
OBJECT IDENTIFIER    

cpqCmcSetupInput4 1.3.6.1.4.1.232.153.2.2.2.1.2.10
OBJECT IDENTIFIER    

cpqCmcSetupLock1 1.3.6.1.4.1.232.153.2.2.2.1.2.11
OBJECT IDENTIFIER    

cpqCmcSetupLock2 1.3.6.1.4.1.232.153.2.2.2.1.2.12
OBJECT IDENTIFIER    

cpqCmcSetupSmoke 1.3.6.1.4.1.232.153.2.2.2.1.2.13
OBJECT IDENTIFIER    

cpqCmcSetupShock 1.3.6.1.4.1.232.153.2.2.2.1.2.14
OBJECT IDENTIFIER    

cpqCmcSetupAux1 1.3.6.1.4.1.232.153.2.2.2.1.2.15
OBJECT IDENTIFIER    

cpqCmcSetupAux2 1.3.6.1.4.1.232.153.2.2.2.1.2.16
OBJECT IDENTIFIER    

cpqCmcSetupAlarm1 1.3.6.1.4.1.232.153.2.2.2.1.2.17
OBJECT IDENTIFIER    

cpqCmcSetupAlarm2 1.3.6.1.4.1.232.153.2.2.2.1.2.18
OBJECT IDENTIFIER    

cpqCmcSetupClock 1.3.6.1.4.1.232.153.2.2.2.1.3
OBJECT IDENTIFIER    

cpqCmcSetupThreshold 1.3.6.1.4.1.232.153.2.2.2.2
OBJECT IDENTIFIER    

cpqCmcTraps 1.3.6.1.4.1.232.153.2.2.2.3
OBJECT IDENTIFIER    

cpqCmcValues 1.3.6.1.4.1.232.153.2.2.3
OBJECT IDENTIFIER    

cpqCmcStatus 1.3.6.1.4.1.232.153.2.2.4
OBJECT IDENTIFIER    

cpqCmcControl 1.3.6.1.4.1.232.153.2.2.5
OBJECT IDENTIFIER    

cpqCmcLog 1.3.6.1.4.1.232.153.2.2.6
OBJECT IDENTIFIER    

cpqCmcMibRevMajor 1.3.6.1.4.1.232.153.1.1
The Major Revision level. A change in the major revision level represents a major change in the architecture of the MIB. A change in the major revision level may indicate a significant change in the information, correct interpretation of data may require a MIB document with the same major revision level.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..65535  

cpqCmcMibRevMinor 1.3.6.1.4.1.232.153.1.2
The Minor Revision level. A change in the minor revision level may represent some minor additional support, no changes to any pre-existing information has occurred.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..65535  

cpqCmcMibCondition 1.3.6.1.4.1.232.153.1.3
The overall condition (status) of the system (rack(s)) represented by this MIB. (2) OK (3) a minor problem, warning condition (yellow LED on CMC) (4) a major problem (red LED on CMC)
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER other(1), ok(2), degraded(3), failed(4)  

cpqCmcOsCommonPollFreq 1.3.6.1.4.1.232.153.2.1.1.1
The Insight Agent's polling frequency. The frequency, in seconds, at which the Insight Agent requests information from the device driver. A frequency of zero (0) indicates that the Insight Agent retrieves the information upon request of a management station, it does not poll the device driver at a specific interval.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..65535  

cpqCmcDeviceCondition 1.3.6.1.4.1.232.153.2.2.1
Condition of CMC device, (3) an overload of the 24V DC supply to the connected accessories occurred (4) the overload-protection (fuse) has released
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER other(1), ok(2), overloadDC(3), fuseDC(4)  

cpqCmcsetLanguage 1.3.6.1.4.1.232.153.2.2.2.1.1.1
Language of LCD
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), english(2), french(3), italian(4), german(5), spanish(6), dutch(7), japanese(8)  

cpqCmcsetTempUnit 1.3.6.1.4.1.232.153.2.2.2.1.1.2
Unit of all temperature values and thresholds, Celsius or Fahrenheit
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), celsius(2), fahrenheit(3)  

cpqCmcsetAudibleAlarm 1.3.6.1.4.1.232.153.2.2.2.1.1.3
Audible alarm in CMC unit: (2): silencing with button on CMC is enabled (3): silencing with button on CMC is disabled (4): audible alarm is off (general). On/off of audible alarm for each event is possible in cpqCmcsetupEvents-group
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), enableSilence(2), disableSilence(3), off(4)  

cpqCmcPassword 1.3.6.1.4.1.232.153.2.2.2.1.1.4
Password to get access to terminal or LCD
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..6)  

cpqCmcPasswordOption 1.3.6.1.4.1.232.153.2.2.2.1.1.5
Enable or disable password entry to get access to terminal or LCD
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), enabled(2), disabled(3)  

cpqCmcquitRelay1 1.3.6.1.4.1.232.153.2.2.2.1.1.6
Enable or disable acknowledging currently active alarm relay 1 (with 'ENTER' on CMC).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), enabled(2), disabled(3)  

cpqCmcquitRelay2 1.3.6.1.4.1.232.153.2.2.2.1.1.7
Enable or disable acknowledging currently active alarm relay 2 (with 'ENTER' on CMC).
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), enabled(2), disabled(3)  

cpqCmclogicRelay1 1.3.6.1.4.1.232.153.2.2.2.1.1.8
Logic of Relay 1: (2) Relay will pick up in case of an alarm (3) Relay will release in case of an alarm (4) not used
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), closeAtAlarm(2), openAtAlarm(3), closeAtEPO(4)  

cpqCmclogicRelay2 1.3.6.1.4.1.232.153.2.2.2.1.1.9
Logic of Relay 2: (2) Relay will pick up in case of an alarm (3) Relay will release in case of an alarm (4) not used
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), closeAtAlarm(2), openAtAlarm(3), closeAtEPO(4)  

cpqCmcSetupTemp1Avail 1.3.6.1.4.1.232.153.2.2.2.1.2.1.1
Temperature sensor: (2) sensor available (3) sensor not available
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), available(2), notAvailable(3)  

cpqCmcSetupTemp1RelaysWarn 1.3.6.1.4.1.232.153.2.2.2.1.2.1.2
Alert handling of Alarm Relays in case of warning condition of temperature sensor 1: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) both Relays will switch
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), off(2), relay1(3), relay2(4), both(5)  

cpqCmcSetupTemp1RelaysMax 1.3.6.1.4.1.232.153.2.2.2.1.2.1.3
Alert handling of Alarm Relays in case of max. alarm condition of temperature sensor 1: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) both Relays will switch
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), off(2), relay1(3), relay2(4), both(5)  

cpqCmcSetupTemp1RelaysMin 1.3.6.1.4.1.232.153.2.2.2.1.2.1.4
Alert handling of Alarm Relays in case of min. alarm condition of temperature sensor 1: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) both Relays will switch
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), off(2), relay1(3), relay2(4), both(5)  

cpqCmcSetupTemp1AudibleAlarmWarn 1.3.6.1.4.1.232.153.2.2.2.1.2.1.5
Alert handling of Audible Alarm of in case of warning condition of temperature sensor 1: (2) Start Audible Alarm (3) No Audible Alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), enabled(2), disabled(3)  

cpqCmcSetupTemp1AudibleAlarmMax 1.3.6.1.4.1.232.153.2.2.2.1.2.1.6
Alert handling of Audible Alarm of in case of max. alarm condition of temperature sensor 1: (2) Start Audible Alarm (3) No Audible Alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), enabled(2), disabled(3)  

cpqCmcSetupTemp1AudibleAlarmMin 1.3.6.1.4.1.232.153.2.2.2.1.2.1.7
Alert handling of Audible Alarm of in case of min. alarm condition of temperature sensor 1: (2) Start Audible Alarm (3) No Audible Alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), enabled(2), disabled(3)  

cpqCmcSetupTemp2Avail 1.3.6.1.4.1.232.153.2.2.2.1.2.2.1
Temperature sensor: (2) sensor available (3) sensor not available
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), available(2), notAvailable(3)  

cpqCmcSetupTemp2RelaysWarn 1.3.6.1.4.1.232.153.2.2.2.1.2.2.2
Alert handling of Alarm Relays in case of warning condition of temperature sensor 2: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) both Relays will switch
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), off(2), relay1(3), relay2(4), both(5)  

cpqCmcSetupTemp2RelaysMax 1.3.6.1.4.1.232.153.2.2.2.1.2.2.3
Alert handling of Alarm Relays in case of max. alarm condition of temperature sensor 2: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) both Relays will switch
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), off(2), relay1(3), relay2(4), both(5)  

cpqCmcSetupTemp2RelaysMin 1.3.6.1.4.1.232.153.2.2.2.1.2.2.4
Alert handling of Alarm Relays in case of min. alarm condition of temperature sensor 2: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) both Relays will switch
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), off(2), relay1(3), relay2(4), both(5)  

cpqCmcSetupTemp2AudibleAlarmWarn 1.3.6.1.4.1.232.153.2.2.2.1.2.2.5
Alert handling of Audible Alarm of in case of warning condition of temperature sensor 2: (2) Start Audible Alarm (3) No Audible Alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), enabled(2), disabled(3)  

cpqCmcSetupTemp2AudibleAlarmMax 1.3.6.1.4.1.232.153.2.2.2.1.2.2.6
Alert handling of Audible Alarm of in case of max. alarm condition of temperature sensor 2: (2) Start Audible Alarm (3) No Audible Alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), enabled(2), disabled(3)  

cpqCmcSetupTemp2AudibleAlarmMin 1.3.6.1.4.1.232.153.2.2.2.1.2.2.7
Alert handling of Audible Alarm of in case of min. alarm condition of temperature sensor 2: (2) Start Audible Alarm (3) No Audible Alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), enabled(2), disabled(3)  

cpqCmcSetupFan1Avail 1.3.6.1.4.1.232.153.2.2.2.1.2.3.1
Fan 1: (2) Fan 1 available (3) Fan 1 not available
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), available(2), notAvailable(3)  

cpqCmcSetupFan1Relays 1.3.6.1.4.1.232.153.2.2.2.1.2.3.2
Alert handling of Alarm Relays in case of alarm condition of Fan 1: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) both Relays will switch
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), off(2), relay1(3), relay2(4), both(5)  

cpqCmcSetupFan1AudibleAlarm 1.3.6.1.4.1.232.153.2.2.2.1.2.3.3
Alert handling of Audible Alarm of in case of alarm condition of Fan 1: (2) Start Audible Alarm (3) No Audible Alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), enabled(2), disabled(3)  

cpqCmcSetupFan2Avail 1.3.6.1.4.1.232.153.2.2.2.1.2.4.1
Fan 2: (2) Fan 2 available (3) Fan 2 not available
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), available(2), notAvailable(3)  

cpqCmcSetupFan2Relays 1.3.6.1.4.1.232.153.2.2.2.1.2.4.2
Alert handling of Alarm Relays in case of alarm condition of Fan 2: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) both Relays will switch
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), off(2), relay1(3), relay2(4), both(5)  

cpqCmcSetupFan2AudibleAlarm 1.3.6.1.4.1.232.153.2.2.2.1.2.4.3
Alert handling of Audible Alarm of in case of alarm condition of Fan 2: (2) Start Audible Alarm (3) No Audible Alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), enabled(2), disabled(3)  

cpqCmcSetupVoltageAvail 1.3.6.1.4.1.232.153.2.2.2.1.2.5.1
Voltage monitoring: (2) available (3) not available
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), available(2), notAvailable(3)  

cpqCmcSetupVoltageRelaysMax 1.3.6.1.4.1.232.153.2.2.2.1.2.5.2
Alert handling of Alarm Relays in case of max. alarm condition of voltage monitoring: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) both Relays will switch
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), off(2), relay1(3), relay2(4), both(5)  

cpqCmcSetupVoltageRelaysMin 1.3.6.1.4.1.232.153.2.2.2.1.2.5.3
Alert handling of Alarm Relays in case of min. alarm condition of voltage monitoring: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) both Relays will switch
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), off(2), relay1(3), relay2(4), both(5)  

cpqCmcSetupVoltageAudibleAlarmMax 1.3.6.1.4.1.232.153.2.2.2.1.2.5.4
Alert handling of Audible Alarm of in case of max. alarm condition of voltage monitoring: (2) Start Audible Alarm (3) No Audible Alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), enabled(2), disabled(3)  

cpqCmcSetupVoltageAudibleAlarmMin 1.3.6.1.4.1.232.153.2.2.2.1.2.5.5
Alert handling of Audible Alarm of in case of min. alarm condition of voltage monitoring: (2) Start Audible Alarm (3) No Audible Alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), enabled(2), disabled(3)  

cpqCmcSetupHumidityAvail 1.3.6.1.4.1.232.153.2.2.2.1.2.6.1
Humidity sensor: (2) available (3) not available
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), available(2), notAvailable(3)  

cpqCmcSetupHumidityRelaysMax 1.3.6.1.4.1.232.153.2.2.2.1.2.6.2
Alert handling of Alarm Relays in case of max. alarm condition of humidity monitoring: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) both Relays will switch
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), off(2), relay1(3), relay2(4), both(5)  

cpqCmcSetupHumidityRelaysMin 1.3.6.1.4.1.232.153.2.2.2.1.2.6.3
Alert handling of Alarm Relays in case of min. alarm condition of humidity monitoring: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) both Relays will switch
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), off(2), relay1(3), relay2(4), both(5)  

cpqCmcSetupHumidityAudibleAlarmMax 1.3.6.1.4.1.232.153.2.2.2.1.2.6.4
Alert handling of Audible Alarm of in case of max. alarm condition of humidity monitoring: (2) Start Audible Alarm (3) No Audible Alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), enabled(2), disabled(3)  

cpqCmcSetupHumidityAudibleAlarmMin 1.3.6.1.4.1.232.153.2.2.2.1.2.6.5
Alert handling of Audible Alarm of in case of min. alarm condition of humidity monitoring: (2) Start Audible Alarm (3) No Audible Alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), enabled(2), disabled(3)  

cpqCmcSetupInput1Avail 1.3.6.1.4.1.232.153.2.2.2.1.2.7.1
Input 1 sensor: (2) available (3) not available
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), available(2), notAvailable(3)  

cpqCmcSetupInput1Relays 1.3.6.1.4.1.232.153.2.2.2.1.2.7.2
Alert handling of Alarm Relays in case of a warning condition of Input 1 (Door/Sidewall open): (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) both Relays will switch
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), off(2), relay1(3), relay2(4), both(5)  

cpqCmcSetupInput1AudibleAlarm 1.3.6.1.4.1.232.153.2.2.2.1.2.7.3
Alert handling of Audible Alarm of in case of a warning condition of Input 1 (Door/Sidewall open): (2) Start Audible Alarm (3) No Audible Alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), enabled(2), disabled(3)  

cpqCmcSetupInput1FansOff 1.3.6.1.4.1.232.153.2.2.2.1.2.7.4
Fan switching off if Door/Sidewall 1 is opened: (2) both fans would be switched off (3) only fan1 will be switched off (4) only fan2 will be switched off (5) no fan will be switched off
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), both(2), fan1(3), fan2(4), noFan(5)  

cpqCmcSetupInput1ShockSensor 1.3.6.1.4.1.232.153.2.2.2.1.2.7.5
Shock sensor function if Door/Sidewall 1 is opened: (2) Shock Sensor is off (disabled) (3) Shock Sensor is on (enabled)
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), off(2), on(3)  

cpqCmcSetupInput1Description 1.3.6.1.4.1.232.153.2.2.2.1.2.7.6
Descriptional text of Input1
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..18)  

cpqCmcSetupInput1Lock 1.3.6.1.4.1.232.153.2.2.2.1.2.7.7
Door/Sidewall 1 is locked by: (2) no locking device (3) locking device 1 (4) locking device 2 (5) both locking devices
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), none(2), lock1(3), lock2(4), both(5)  

cpqCmcSetupInput2Avail 1.3.6.1.4.1.232.153.2.2.2.1.2.8.1
Input 2 sensor: (2) available (3) not available
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), available(2), notAvailable(3)  

cpqCmcSetupInput2Relays 1.3.6.1.4.1.232.153.2.2.2.1.2.8.2
Alert handling of Alarm Relays in case of a warning condition of Input 2 (Door/Sidewall open): (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) both Relays will switch
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), off(2), relay1(3), relay2(4), both(5)  

cpqCmcSetupInput2AudibleAlarm 1.3.6.1.4.1.232.153.2.2.2.1.2.8.3
Alert handling of Audible Alarm of in case of a warning condition of Input 2 (Door/Sidewall open): (2) Start Audible Alarm (3) No Audible Alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), enabled(2), disabled(3)  

cpqCmcSetupInput2FansOff 1.3.6.1.4.1.232.153.2.2.2.1.2.8.4
Fan switching off if Door/Sidewall 2 is opened: (2) both fans would be switched off (3) only fan1 will be switched off (4) only fan2 will be switched off (5) no fan will be switched off
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), both(2), fan1(3), fan2(4), noFan(5)  

cpqCmcSetupInput2ShockSensor 1.3.6.1.4.1.232.153.2.2.2.1.2.8.5
Shock sensor function if Door/Sidewall 2 is opened: (2) Shock Sensor is off (disabled) (3) Shock Sensor is on (enabled)
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), off(2), on(3)  

cpqCmcSetupInput2Description 1.3.6.1.4.1.232.153.2.2.2.1.2.8.6
Descriptional text of Input2
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..18)  

cpqCmcSetupInput2Lock 1.3.6.1.4.1.232.153.2.2.2.1.2.8.7
Door/Sidewall 2 is locked by: (2) no locking device (3) locking device 1 (4) locking device 2 (5) both locking devices
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), none(2), lock1(3), lock2(4), both(5)  

cpqCmcSetupInput3Avail 1.3.6.1.4.1.232.153.2.2.2.1.2.9.1
Input 3 sensor: (2) available (3) not available
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), available(2), notAvailable(3)  

cpqCmcSetupInput3Relays 1.3.6.1.4.1.232.153.2.2.2.1.2.9.2
Alert handling of Alarm Relays in case of a warning condition of Input 3 (Door/Sidewall open): (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) both Relays will switch
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), off(2), relay1(3), relay2(4), both(5)  

cpqCmcSetupInput3AudibleAlarm 1.3.6.1.4.1.232.153.2.2.2.1.2.9.3
Alert handling of Audible Alarm of in case of a warning condition of Input 3 (Door/Sidewall open): (2) Start Audible Alarm (3) No Audible Alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), enabled(2), disabled(3)  

cpqCmcSetupInput3FansOff 1.3.6.1.4.1.232.153.2.2.2.1.2.9.4
Fan switching off if Door/Sidewall 3 is opened: (2) both fans would be switched off (3) only fan1 will be switched off (4) only fan2 will be switched off (5) no fan will be switched off
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), both(2), fan1(3), fan2(4), noFan(5)  

cpqCmcSetupInput3ShockSensor 1.3.6.1.4.1.232.153.2.2.2.1.2.9.5
Shock sensor function if Door/Sidewall 3 is opened: (2) Shock Sensor is off (disabled) (3) Shock Sensor is on (enabled)
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), off(2), on(3)  

cpqCmcSetupInput3Description 1.3.6.1.4.1.232.153.2.2.2.1.2.9.6
Descriptional text of Input3
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..18)  

cpqCmcSetupInput3Lock 1.3.6.1.4.1.232.153.2.2.2.1.2.9.7
Door/Sidewall 3 is locked by: (2) no locking device (3) locking device 1 (4) locking device 2 (5) both locking devices
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), none(2), lock1(3), lock2(4), both(5)  

cpqCmcSetupInput4Avail 1.3.6.1.4.1.232.153.2.2.2.1.2.10.1
Input 4 sensor: (2) available (3) not available
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), available(2), notAvailable(3)  

cpqCmcSetupInput4Relays 1.3.6.1.4.1.232.153.2.2.2.1.2.10.2
Alert handling of Alarm Relays in case of a warning condition of Input 4 (Door/Sidewall open): (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) both Relays will switch
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), off(2), relay1(3), relay2(4), both(5)  

cpqCmcSetupInput4AudibleAlarm 1.3.6.1.4.1.232.153.2.2.2.1.2.10.3
Alert handling of Audible Alarm of in case of a warning condition of Input 4 (Door/Sidewall open): (2) Start Audible Alarm (3) No Audible Alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), enabled(2), disabled(3)  

cpqCmcSetupInput4FansOff 1.3.6.1.4.1.232.153.2.2.2.1.2.10.4
Fan switching off if Door/Sidewall 4 is opened: (2) both fans would be switched off (3) only fan1 will be switched off (4) only fan2 will be switched off (5) no fan will be switched off
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), both(2), fan1(3), fan2(4), noFan(5)  

cpqCmcSetupInput4ShockSensor 1.3.6.1.4.1.232.153.2.2.2.1.2.10.5
Shock sensor function if Door/Sidewall 4 is opened: (2) Shock Sensor is off (disabled) (3) Shock Sensor is on (enabled)
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), off(2), on(3)  

cpqCmcSetupInput4Description 1.3.6.1.4.1.232.153.2.2.2.1.2.10.6
Descriptional text of Input4
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..18)  

cpqCmcSetupInput4Lock 1.3.6.1.4.1.232.153.2.2.2.1.2.10.7
Door/Sidewall 4 is locked by: (2) no locking device (3) locking device 1 (4) locking device 2 (5) both locking devices
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), none(2), lock1(3), lock2(4), both(5)  

cpqCmcSetupLock1Avail 1.3.6.1.4.1.232.153.2.2.2.1.2.11.1
Door locking device 1: (2) device available (3) device not available, no alarm, if door is not locked
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), available(2), notAvailable(3)  

cpqCmcSetupLock1Relays 1.3.6.1.4.1.232.153.2.2.2.1.2.11.2
Alert handling of Alarm Relays in case of an alarm condition of Lock 1 (door not locked..): (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) both Relays will switch
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), off(2), relay1(3), relay2(4), both(5)  

cpqCmcSetupLock1RelaysDevice 1.3.6.1.4.1.232.153.2.2.2.1.2.11.3
Alert handling of Alarm Relays in case of an alarm condition of Locking device 1 (power fail, low battery...): (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) both Relays will switch
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), off(2), relay1(3), relay2(4), both(5)  

cpqCmcSetupLock1AudibleAlarm 1.3.6.1.4.1.232.153.2.2.2.1.2.11.4
Alert handling of Audible Alarm of in case of an alarm condition of Lock 1: (2) Start Audible Alarm (3) No Audible Alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), enabled(2), disabled(3)  

cpqCmcSetupLock1AudibleAlarmDevice 1.3.6.1.4.1.232.153.2.2.2.1.2.11.5
Alert handling of Audible Alarm of in case of an alarm condition of Locking device 1 (power fail, low battery..): (2) Start Audible Alarm (3) No Audible Alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), enabled(2), disabled(3)  

cpqCmcSetupLock1Time 1.3.6.1.4.1.232.153.2.2.2.1.2.11.6
Time in seconds while the lock 1 is unlocked after getting an unlock-command
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 3..600  

cpqCmcSetupLock1PwrFailUnlock 1.3.6.1.4.1.232.153.2.2.2.1.2.11.7
Unlock door in case of power fail of locking device: (2) disabled (3) auto unlock the door (4) unlock door with remote signal
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), disabled(2), auto(3), manual(4)  

cpqCmcSetupLock1BattLowUnlock 1.3.6.1.4.1.232.153.2.2.2.1.2.11.8
Unlock door in case of low battery of locking device: (2) disabled (3) auto unlock the door (4) unlock door with remote signal
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), disabled(2), auto(3), manual(4)  

cpqCmcSetupLock1NetFailUnlock 1.3.6.1.4.1.232.153.2.2.2.1.2.11.9
Unlock door in case of network failure: (2) disabled (3) auto unlock the door (4) unlock door with remote signal
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), disabled(2), auto(3), manual(4)  

cpqCmcSetupLock1LifeFailUnlock 1.3.6.1.4.1.232.153.2.2.2.1.2.11.10
Unlock door in case of lifecheck failure (connection CMC<->locking device): (2) disabled (3) auto unlock the door (4) unlock door with remote signal
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), disabled(2), auto(3), manual(4)  

cpqCmcSetupLock2Avail 1.3.6.1.4.1.232.153.2.2.2.1.2.12.1
Door locking device 2: (2) device available (3) device not available, no alarm, if door is not locked
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), available(2), notAvailable(3)  

cpqCmcSetupLock2Relays 1.3.6.1.4.1.232.153.2.2.2.1.2.12.2
Alert handling of Alarm Relays in case of an alarm condition of Lock 2 (door not locked..): (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) both Relays will switch
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), off(2), relay1(3), relay2(4), both(5)  

cpqCmcSetupLock2RelaysDevice 1.3.6.1.4.1.232.153.2.2.2.1.2.12.3
Alert handling of Alarm Relays in case of an alarm condition of Locking device 2 (power fail, low battery...): (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) both Relays will switch
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), off(2), relay1(3), relay2(4), both(5)  

cpqCmcSetupLock2AudibleAlarm 1.3.6.1.4.1.232.153.2.2.2.1.2.12.4
Alert handling of Audible Alarm of in case of an alarm condition of Lock 2: (2) Start Audible Alarm (3) No Audible Alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), enabled(2), disabled(3)  

cpqCmcSetupLock2AudibleAlarmDevice 1.3.6.1.4.1.232.153.2.2.2.1.2.12.5
Alert handling of Audible Alarm of in case of an alarm condition of Locking device 2 (power fail, low battery..): (2) Start Audible Alarm (3) No Audible Alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), enabled(2), disabled(3)  

cpqCmcSetupLock2Time 1.3.6.1.4.1.232.153.2.2.2.1.2.12.6
Time in seconds while the lock 2 is unlocked after getting an unlock-command
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 3..600  

cpqCmcSetupLock2PwrFailUnlock 1.3.6.1.4.1.232.153.2.2.2.1.2.12.7
Unlock door in case of power fail of locking device: (2) disabled (3) auto unlock the door (4) unlock door with remote signal
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), disabled(2), auto(3), manual(4)  

cpqCmcSetupLock2BattLowUnlock 1.3.6.1.4.1.232.153.2.2.2.1.2.12.8
Unlock door in case of low battery of locking device: (2) disabled (3) auto unlock the door (4) unlock door with remote signal
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), disabled(2), auto(3), manual(4)  

cpqCmcSetupLock2NetFailUnlock 1.3.6.1.4.1.232.153.2.2.2.1.2.12.9
Unlock door in case of network failure: (2) disabled (3) auto unlock the door (4) unlock door with remote signal
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), disabled(2), auto(3), manual(4)  

cpqCmcSetupLock2LifeFailUnlock 1.3.6.1.4.1.232.153.2.2.2.1.2.12.10
Unlock door in case of lifecheck failure (connection CMC<->locking device): (2) disabled (3) auto unlock the door (4) unlock door with remote signal
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), disabled(2), auto(3), manual(4)  

cpqCmcSetupSmokeAvail 1.3.6.1.4.1.232.153.2.2.2.1.2.13.1
Smoke sensor: (2) available (3) not available
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), available(2), notAvailable(3)  

cpqCmcSetupSmokeRelays 1.3.6.1.4.1.232.153.2.2.2.1.2.13.2
Alert handling of Alarm Relays in case of an alarm condition of Smoke Sensor: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) both Relays will switch
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), off(2), relay1(3), relay2(4), both(5)  

cpqCmcSetupSmokeAudibleAlarm 1.3.6.1.4.1.232.153.2.2.2.1.2.13.3
Alert handling of Audible Alarm of in case of an alarm condition of Smoke Sensor: (2) Start Audible Alarm (3) No Audible Alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), enabled(2), disabled(3)  

cpqCmcSetupSmokeFansOff 1.3.6.1.4.1.232.153.2.2.2.1.2.13.4
Fan switching off if in case of smoke-alarm: (2) both fans would be switched off (3) only fan1 will be switched off (4) only fan2 will be switched off (5) no fan will be switched off
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), both(2), fan1(3), fan2(4), noFan(5)  

cpqCmcSetupSmokeUnlock 1.3.6.1.4.1.232.153.2.2.2.1.2.13.5
Lock is unlocked in case of smoke-alarm: (2) both locks will be unlocked (3) only lock1 will be unlocked (4) only lock2 will be unlocked (5) no lock will be unlocked
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), both(2), lock1(3), lock2(4), noLock(5)  

cpqCmcSetupShockAvail 1.3.6.1.4.1.232.153.2.2.2.1.2.14.1
Shock sensor: (2) available (3) not available
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), available(2), notAvailable(3)  

cpqCmcSetupShockRelays 1.3.6.1.4.1.232.153.2.2.2.1.2.14.2
Alert handling of Alarm Relays in case of an alarm condition of Shock Sensor: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) both Relays will switch
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), off(2), relay1(3), relay2(4), both(5)  

cpqCmcSetupShockAudibleAlarm 1.3.6.1.4.1.232.153.2.2.2.1.2.14.3
Alert handling of Audible Alarm of in case of an alarm condition of Shock Sensor: (2) Start Audible Alarm (3) No Audible Alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), enabled(2), disabled(3)  

cpqCmcSetupShockSensitivity 1.3.6.1.4.1.232.153.2.2.2.1.2.14.4
Sensitivity of shock-sensor. 1 = low sensitivity, 10 = high sensitivity
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..10  

cpqCmcSetupAux1Avail 1.3.6.1.4.1.232.153.2.2.2.1.2.15.1
Aux 1 sensor: (2) available (3) not available
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), available(2), notAvailable(3)  

cpqCmcSetupAux1Relays 1.3.6.1.4.1.232.153.2.2.2.1.2.15.2
Alert handling of Alarm Relays in case of an alarm condition of Aux 1: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) both Relays will switch
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), off(2), relay1(3), relay2(4), both(5)  

cpqCmcSetupAux1AudibleAlarm 1.3.6.1.4.1.232.153.2.2.2.1.2.15.3
Alert handling of Audible Alarm of in case of an alarm condition of Aux 1: (2) Start Audible Alarm (3) No Audible Alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), enabled(2), disabled(3)  

cpqCmcSetupAux1InputType 1.3.6.1.4.1.232.153.2.2.2.1.2.15.4
Type of other digital input (used for any digital signal): (2) contact is normally open, no alarm if contact is open, alarm if contact is closed (3) contact is normally closed, no alarm if contact is closed, alarm if contact is open
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), normOpen(2), normClosed(3)  

cpqCmcSetupAux1Description 1.3.6.1.4.1.232.153.2.2.2.1.2.15.5
Descriptional text of the digital input (Aux1)
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..18)  

cpqCmcSetupAux1Unlock 1.3.6.1.4.1.232.153.2.2.2.1.2.15.6
Lock will be unlocked with Aux-Input 1: (2) no lock will be unlocked (3) only lock1 will be unlocked (4) only lock2 will be unlocked (5) both locks will be unlocked
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), noLock(2), lock1(3), lock2(4), both(5)  

cpqCmcSetupAux2Avail 1.3.6.1.4.1.232.153.2.2.2.1.2.16.1
Aux 2 sensor: (2) available (3) not available
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), available(2), notAvailable(3)  

cpqCmcSetupAux2Relays 1.3.6.1.4.1.232.153.2.2.2.1.2.16.2
Alert handling of Alarm Relays in case of an alarm condition of Aux 2: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) both Relays will switch
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), off(2), relay1(3), relay2(4), both(5)  

cpqCmcSetupAux2AudibleAlarm 1.3.6.1.4.1.232.153.2.2.2.1.2.16.3
Alert handling of Audible Alarm of in case of an alarm condition of Aux 2: (2) Start Audible Alarm (3) No Audible Alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), enabled(2), disabled(3)  

cpqCmcSetupAux2InputType 1.3.6.1.4.1.232.153.2.2.2.1.2.16.4
Type of other digital input (used for any digital signal): (2) contact is normally open, no alarm if contact is open, alarm if contact is closed (3) contact is normally closed, no alarm if contact is closed, alarm if contact is open
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), normOpen(2), normClosed(3)  

cpqCmcSetupAux2Description 1.3.6.1.4.1.232.153.2.2.2.1.2.16.5
Descriptional text of the digital input (Aux2)
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..18)  

cpqCmcSetupAux2Unlock 1.3.6.1.4.1.232.153.2.2.2.1.2.16.6
Lock will be unlocked with Aux-Input 2: (2) no lock will be unlocked (3) only lock1 will be unlocked (4) only lock2 will be unlocked (5) both locks will be unlocked
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), noLock(2), lock1(3), lock2(4), both(5)  

cpqCmcSetupAlarm1Relays 1.3.6.1.4.1.232.153.2.2.2.1.2.17.1
Alert handling of Alarm Relays in case of an alarm condition of Alarm 1: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) both Relays will switch
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), off(2), relay1(3), relay2(4), both(5)  

cpqCmcSetupAlarm1AudibleAlarm 1.3.6.1.4.1.232.153.2.2.2.1.2.17.2
Alert handling of Audible Alarm of in case of an alarm condition of Alarm 1: (2) Start Audible Alarm (3) No Audible Alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), enabled(2), disabled(3)  

cpqCmcSetupAlarm1Description 1.3.6.1.4.1.232.153.2.2.2.1.2.17.3
Descriptional text of alarm 1
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..18)  

cpqCmcSetupAlarm2Relays 1.3.6.1.4.1.232.153.2.2.2.1.2.18.1
Alert handling of Alarm Relays in case of an alarm condition of Alarm 2: (2) no switching of Relays (3) Relay 1 will switch (4) Relay 2 will switch (5) both Relays will switch
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), off(2), relay1(3), relay2(4), both(5)  

cpqCmcSetupAlarm2AudibleAlarm 1.3.6.1.4.1.232.153.2.2.2.1.2.18.2
Alert handling of Audible Alarm of in case of an alarm condition of Alarm 2: (2) Start Audible Alarm (3) No Audible Alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), enabled(2), disabled(3)  

cpqCmcSetupAlarm2Description 1.3.6.1.4.1.232.153.2.2.2.1.2.18.3
Descriptional text of alarm 2
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..18)  

cpqCmcSetupDate 1.3.6.1.4.1.232.153.2.2.2.1.3.1
actual Date in format DD.MM.YYYY
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..10)  

cpqCmcSetupTime 1.3.6.1.4.1.232.153.2.2.2.1.3.2
actual Time in format HH:MM:SS, HH (0-23), MM (0-59), SS (0-59)
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..8)  

cpqCmcThresholdMaxTemp1 1.3.6.1.4.1.232.153.2.2.2.2.1
Threshold value maximum temperature 1
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..200  

cpqCmcThresholdWarningTemp1 1.3.6.1.4.1.232.153.2.2.2.2.2
Threshold value warning temperature 1
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..200  

cpqCmcThresholdMinTemp1 1.3.6.1.4.1.232.153.2.2.2.2.3
Threshold value minimum temperature 1
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..100  

cpqCmcThresholdMaxTemp2 1.3.6.1.4.1.232.153.2.2.2.2.4
Threshold value maximum temperature 2
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..200  

cpqCmcThresholdWarningTemp2 1.3.6.1.4.1.232.153.2.2.2.2.5
Threshold value warning temperature 2
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..200  

cpqCmcThresholdMinTemp2 1.3.6.1.4.1.232.153.2.2.2.2.6
Threshold value minimum temperature 2
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..100  

cpqCmcThresholdFan1 1.3.6.1.4.1.232.153.2.2.2.2.7
Threshold Fan 1 in deg F or deg C, Fan 1 will start if temperature 1 exceeds this value
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..200  

cpqCmcThresholdFan1Hysteresis 1.3.6.1.4.1.232.153.2.2.2.2.8
Hystersis of Fan 1, Fan 1 will stop if temperature 1 falls below value of cpqCmcThresholdFan1 minus cpqCmcThresholdFan1Hysteresis
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..20  

cpqCmcThresholdFan2 1.3.6.1.4.1.232.153.2.2.2.2.9
Threshold Fan 2 in deg F or deg C, Fan 2 will start if temperature 2 exceeds this value
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..200  

cpqCmcThresholdFan2Hysteresis 1.3.6.1.4.1.232.153.2.2.2.2.10
Hystersis of Fan 2, Fan 2 will stop if temperature 2 falls below value of cpqCmcThresholdFan2 minus cpqCmcThresholdFan2Hysteresis
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 1..20  

cpqCmcThresholdMaxVoltage 1.3.6.1.4.1.232.153.2.2.2.2.11
Threshold high value Voltage alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..255  

cpqCmcThresholdMinVoltage 1.3.6.1.4.1.232.153.2.2.2.2.12
Threshold low value Voltage alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..255  

cpqCmcThresholdMaxHumidity 1.3.6.1.4.1.232.153.2.2.2.2.13
Threshold high value Humidity alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..100  

cpqCmcThresholdMinHumidity 1.3.6.1.4.1.232.153.2.2.2.2.14
Threshold low value Humidity alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..100  

cpqCmcTrapTableNumber 1.3.6.1.4.1.232.153.2.2.2.3.1
Number of trapTable entries. The number of trap-receivers
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

cpqCmcTrapTable 1.3.6.1.4.1.232.153.2.2.2.3.2
A list of trap-receiver entries
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CpqCmcTrapEntry

cpqCmcTrapEntry 1.3.6.1.4.1.232.153.2.2.2.3.2.1
Entries of trapTable
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  CpqCmcTrapEntry  

cpqCmcTrapIndex 1.3.6.1.4.1.232.153.2.2.2.3.2.1.1
Index for the trap-receiver-table. Its value ranges between 1 and the value of cpqCmcTrapTableNumber
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..4  

cpqCmcTrapStatus 1.3.6.1.4.1.232.153.2.2.2.3.2.1.2
Enable or disable trap receiver
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), enabled(2), disabled(3)  

cpqCmcTrapIPaddress 1.3.6.1.4.1.232.153.2.2.2.3.2.1.3
IP-address of trap-receiver
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..15)  

cpqCmcValueTemp1 1.3.6.1.4.1.232.153.2.2.3.1
Actual temperature value of temperature sensor 1 in deg C or deg F
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

cpqCmcValueTemp2 1.3.6.1.4.1.232.153.2.2.3.2
Actual temperature value of temperature sensor 2 in deg C or deg F
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

cpqCmcValueVoltage 1.3.6.1.4.1.232.153.2.2.3.3
Actual value of power supply (voltage monitoring and fans) in V
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

cpqCmcValueHumidity 1.3.6.1.4.1.232.153.2.2.3.4
Actual value of humidity 0..100%
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

cpqCmcValueOperatingTime 1.3.6.1.4.1.232.153.2.2.3.5
Operating time CMC-unit
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

cpqCmcStatusTemp1 1.3.6.1.4.1.232.153.2.2.4.1
The status of temperature 1, see thresholds of temperature 1: (2) temperature normal (3) temperature exceeds warning threshold (4) temperature exceeds max. threshold (5) temperature drops under min. threshold (6) no sensor connected, not available (7) error, sensor disconnected
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER other(1), normal(2), warning(3), overMax(4), underMin(5), noSensor(6), error(7)  

cpqCmcStatusTemp2 1.3.6.1.4.1.232.153.2.2.4.2
The status of temperature 2, see thresholds of temperature 2: (2) temperature normal (3) temperature exceeds warning threshold (4) temperature exceeds max. threshold (5) temperature drops under min. threshold (6) no sensor connected, not available (7) error, sensor disconnected
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER other(1), normal(2), warning(3), overMax(4), underMin(5), noSensor(6), error(7)  

cpqCmcStatusFan1 1.3.6.1.4.1.232.153.2.2.4.3
The status of fan 1: (2) fan is switched off by temperature sensor 1 (3) fan is switched on by temperature sensor 1 (4) fan is switched off by Manual Control (cpqCmcSetFan1) (5) fan is switched on by Manual Control (cpqCmcSetFan1) (6) fan is switched off because of smoke alarm (7) fan is switched off because door is open (8) no fan (9) fan error, current monitoring
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER other(1), autoOff(2), autoOn(3), manualOff(4), manualOn(5), smokeOff(6), doorOff(7), noFan(8), error(9)  

cpqCmcStatusFan2 1.3.6.1.4.1.232.153.2.2.4.4
The status of fan 2: (2) fan is switched off by temperature sensor 2 (3) fan is switched on by temperature sensor 2 (4) fan is switched off by Manual Control (cpqCmcSetFan2) (5) fan is switched on by Manual Control (cpqCmcSetFan2) (6) fan is switched off because of smoke alarm (7) fan is switched off because door is open (8) no fan (9) fan error, current monitoring
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER other(1), autoOff(2), autoOn(3), manualOff(4), manualOn(5), smokeOff(6), doorOff(7), noFan(8), error(9)  

cpqCmcStatusVoltage 1.3.6.1.4.1.232.153.2.2.4.5
The voltage-status, see thresholds of power supply: (2) voltage normal (3) voltage exceeds max. threshold (4) voltage drops under min. threshold (5) no power connected
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER other(1), normal(2), overMax(3), underMin(4), noVoltage(5)  

cpqCmcStatusHumidity 1.3.6.1.4.1.232.153.2.2.4.6
The humidity-status, see thresholds of humidity: (2) humidity normal (3) humidity exceeds max. threshold (4) humidity drops under min. threshold (5) no sensor connected, not available (6) error, sensor disconnected
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER other(1), normal(2), overMax(3), underMin(4), noSensor(5), error(6)  

cpqCmcStatusInput1 1.3.6.1.4.1.232.153.2.2.4.7
The status of door/sidepanel 1, closed (2), open (3) or no sensor connected (4)
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER other(1), closed(2), open(3), noSensor(4)  

cpqCmcStatusInput2 1.3.6.1.4.1.232.153.2.2.4.8
The status of door/sidepanel 2, closed (2), open (3) or no sensor connected (4)
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER other(1), closed(2), open(3), noSensor(4)  

cpqCmcStatusInput3 1.3.6.1.4.1.232.153.2.2.4.9
The status of door/sidepanel 3, closed (2), open (3) or no sensor connected (4)
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER other(1), closed(2), open(3), noSensor(4)  

cpqCmcStatusInput4 1.3.6.1.4.1.232.153.2.2.4.10
The status of door/sidepanel 4, closed (2), open (3) or no sensor connected (4)
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER other(1), closed(2), open(3), noSensor(4)  

cpqCmcStatusLock1Lock 1.3.6.1.4.1.232.153.2.2.4.11
The status of door locking 1 (2) Door locking-device is activated, door is locked (3) Door locking-device is not activated, door is unlocked by Network Management (4) Door locking-device is not activated for x sec, time see cpqCmcSetupLock1Time, door is unlocked by Network Management (5) Door locking-device is not activated, door is unlocked because of Smoke alarm (6) Door is unlocked from remote-signal (7) Door locking-device is not activated, door is unlocked because of Power Fail of locking device (8) Door locking-device is not activated, door is unlocked because of low Battery of locking device (9) Door locking-device is not activated, door is unlocked because of Network Fail (10)Door locking-device is not activated, door is unlocked because of connection fail, no connection locking device <-> CMC (11)Door locking-device is ready to lock, lock will be activated after doors are closed (12)Door locking-device is activated but door is not locked, alarm (13)Configuration error, association door to locking-device missing (14)Lock not installed
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER other(1), locked(2), unlockedAuto(3), unlockedTime(4), unlockedSmoke(5), unlockedKey(6), unlockedPwrFail(7), unlockedBattLow(8), unlockedNetFail(9), unlockedConnFail(10), readyToLock(11), alarm(12), configError(13), notAvail(14)  

cpqCmcStatusLock2Lock 1.3.6.1.4.1.232.153.2.2.4.12
The status of door locking 2 (2) Door locking-device is activated, door is locked (3) Door locking-device is not activated, door is unlocked by Network Management (4) Door locking-device is not activated for x sec, time see cpqCmcSetupLock1Time, door is unlocked by Network Management (5) Door locking-device is not activated, door is unlocked because of Smoke alarm (6) Door is unlocked from remote-signal (7) Door locking-device is not activated, door is unlocked because of Power Fail of locking device (8) Door locking-device is not activated, door is unlocked because of low Battery of locking device (9) Door locking-device is not activated, door is unlocked because of Network Fail (10)Door locking-device is not activated, door is unlocked because of connection fail, no connection locking device <-> CMC (11)Door locking-device is ready to lock, lock will be activated after doors are closed (12)Door locking-device is activated but door is not locked, alarm (13)Configuration error, association door to locking-device missing (14)Lock not installed
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER other(1), locked(2), unlockedAuto(3), unlockedTime(4), unlockedSmoke(5), unlockedKey(6), unlockedPwrFail(7), unlockedBattLow(8), unlockedNetFail(9), unlockedConnFail(10), readyToLock(11), alarm(12), configError(13), notAvail(14)  

cpqCmcStatusSmoke 1.3.6.1.4.1.232.153.2.2.4.13
Status smoke-sensor, OK (2), smoke detected (3) or no sensor connected (4)
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER other(1), cleared(2), present(3), noSensor(4)  

cpqCmcStatusShock 1.3.6.1.4.1.232.153.2.2.4.14
Status Shock sensor, OK (2), shock detected (3) or no sensor connected (4)
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER other(1), cleared(2), present(3), noSensor(4)  

cpqCmcStatusAux1 1.3.6.1.4.1.232.153.2.2.4.15
Status aux. digital input
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER other(1), ok(2), alarm(3), noSensor(4)  

cpqCmcStatusAux2 1.3.6.1.4.1.232.153.2.2.4.16
Status aux. digital input
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER other(1), ok(2), alarm(3), noSensor(4)  

cpqCmcStatusAlarm1 1.3.6.1.4.1.232.153.2.2.4.17
Status of alarm 1, see cmpCmcsetAlarm1. This alarm can be set from the Network management system. A descriptional text for this alarm can be set in cpqCmcSetupAlarm1Description.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER other(1), ok(2), alarm(3)  

cpqCmcStatusAlarm2 1.3.6.1.4.1.232.153.2.2.4.18
Status of alarm 2, see cmpCmcsetAlarm2. This alarm can be set from the Network management system. A descriptional text for this alarm can be set in cpqCmcSetupAlarm2Description.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER other(1), ok(2), alarm(3)  

cpqCmcStatusLock1Dev 1.3.6.1.4.1.232.153.2.2.4.19
The status of door-locking device 1 (2) OK (3) Power fail of door locking-device (4) Low Battery of door locking-device (5) Battery of door locking device needs to be replaced (6) Battery missing, insert all batteries (7) Connection CMC->door locking device lost (8) Lock not installed
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER other(1), ok(2), powerFail(3), lowBattery(4), replaceBatt(5), missingBatt(6), noConnect(7), notAvail(8)  

cpqCmcStatusLock2Dev 1.3.6.1.4.1.232.153.2.2.4.20
The status of door-locking device 2 (2) OK (3) Power fail of door locking-device (4) Low Battery of door locking-device (5) Battery of door locking device needs to be replaced (6) Battery missing, insert all batteries (6) Connection CMC->door locking device lost (7) Lock not installed
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER other(1), ok(2), powerFail(3), lowBattery(4), replaceBatt(5), missingBatt(6), noConnect(7), notAvail(8)  

cpqCmcStatusAccess 1.3.6.1.4.1.232.153.2.2.5.1
Status access, for future use
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..31)  

cpqCmcSetLock1Lock 1.3.6.1.4.1.232.153.2.2.5.2
Set door locking device 1, see table With this command the management-station can set the conditions for the door locking device (2) Door will be locked (3) Door will be unlocked for a defined time, time can be changed, see cpqCmcSetupLock1Time (4) Door is generally unlocked Locking and unlocking with this command can not be enabled or disabled with cpqCmcSetLock1Key-command
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), lockDoor(2), openDoorTime(3), openDoor(4)  

cpqCmcSetLock1Key 1.3.6.1.4.1.232.153.2.2.5.3
Enable or disable unlocking of the rack-door with external components like keypad or remote input. With this command the management station can set the conditions for unlocking the door: (2) unlocking is disabled, no unlocking with keypad or remote input (3) unlocking with keypad or remote signal (both) is enabled (4) unlocking with keypad (only) is enabled (5) unlocking with remote input (only) is enabled Unlocking door with the cpqCmcSetLock1Lock-command does not depend on this variable
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), disable(2), enableBoth(3), enableKeypad(4), enableRemoteInput(5)  

cpqCmcSetLock2Lock 1.3.6.1.4.1.232.153.2.2.5.4
Set door locking device 2, see table With this command the management-station can set the conditions for the door locking device (2) Door will be locked (3) Door will be unlocked for a defined time, time can be changed, see cpqCmcSetupLock2Time (4) Door is generally unlocked Locking and unlocking with this command can not be enabled or disabled with cpqCmcSetLock2Key-command
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), lockDoor(2), openDoorTime(3), openDoor(4)  

cpqCmcSetLock2Key 1.3.6.1.4.1.232.153.2.2.5.5
Enable or disable unlocking of the rack-door with external components like keypad or remote input. With this command the management-station can set the conditions for unlocking the door: (2) unlocking is disabled, no unlocking with keypad or remote input (3) unlocking with keypad or remote signal (both) is enabled (4) unlocking with keypad (only) is enabled (5) unlocking with remote input (only) is enabled Unlocking door with the cpqCmcSetDoor2-command does not depend on this variable
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), disable(2), enableBoth(3), enableKeypad(4), enableRemoteInput(5)  

cpqCmcSetMessage 1.3.6.1.4.1.232.153.2.2.5.6
Set message to CMC, for future use
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..31)  

cpqCmcSetAlarm1 1.3.6.1.4.1.232.153.2.2.5.7
Is used to set an alarm in the CMC from the management-station. With this command the management-station can i.e. switch on an alarm-relay or the AudibleAlarm of the CMC. Can be used for alert-handling
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), clearAlarm(2), setAlarm(3)  

cpqCmcSetAlarm2 1.3.6.1.4.1.232.153.2.2.5.8
Is used to set an alarm in the CMC from the management-station. With this command the management-station can i.e. switch on an alarm-relay or the AudibleAlarm of the CMC. Can be used for alert-handling
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), clearAlarm(2), setAlarm(3)  

cpqCmcSetFan1 1.3.6.1.4.1.232.153.2.2.5.9
Is used for run and stop control of fan1. (2) fan will run and stop according to temperature of sensor 1 and threshold of fan1 (3) fan will run independent of temperature and threshold (4) fan will stop independent of temperature and threshold (3) and (4) can be used for alert handling.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), auto(2), on(3), off(4)  

cpqCmcSetFan2 1.3.6.1.4.1.232.153.2.2.5.10
Is used for run and stop control of fan2. (2) fan will run and stop according to temperature of sensor 2 and threshold of fan2 (3) fan will run independent of temperature and threshold (4) fan will stop independent of temperature and threshold (3) and (4) can be used for alert handling
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), auto(2), on(3), off(4)  

cpqCmcSetQuitRelay1 1.3.6.1.4.1.232.153.2.2.5.11
Status and quit of alarm relay 1. (2) relay is switched because of an alarm (3) relay is not switched, no alarm (4) (set) will quit relay 1 in case of alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), switched(2), notSwitched(3), quit(4)  

cpqCmcSetQuitRelay2 1.3.6.1.4.1.232.153.2.2.5.12
Status and quit of alarm relay 2. (2) relay is switched because of an alarm (3) relay is not switched, no alarm (4) (set) will quit relay 2 in case of alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER other(1), switched(2), notSwitched(3), quit(4)  

cpqCmcLogsNumber 1.3.6.1.4.1.232.153.2.2.6.1
Number of Log-entries
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..100  

cpqCmcLogTable 1.3.6.1.4.1.232.153.2.2.6.2
Log-table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    CpqCmcLogEntry

cpqCmcLogEntry 1.3.6.1.4.1.232.153.2.2.6.2.1
Log-table entries
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  CpqCmcLogEntry  

cpqCmcLogIndex 1.3.6.1.4.1.232.153.2.2.6.2.1.1
Index for the Log-table. Its value ranges between 1 and the value of cpqCmcLogsNumber
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 1..100  

cpqCmcLogDate 1.3.6.1.4.1.232.153.2.2.6.2.1.2
Date of log information.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..11)  

cpqCmcLogTime 1.3.6.1.4.1.232.153.2.2.6.2.1.3
Time of log information.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..11)  

cpqCmcLogText 1.3.6.1.4.1.232.153.2.2.6.2.1.4
Log information.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

cpqCmcLogClass 1.3.6.1.4.1.232.153.2.2.6.2.1.5
Status of log information.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

cpqCmcalarmTemp1 153001
The temperature at rack sensor 1 is outside the specified threshold. Action: Check the air handling system for the rack and refer to Trap Details for more information.
TRAP-TYPE    

cpqCmcalarmTemp2 153002
The temperature at rack sensor 2 is outside the specified threshold. Action: Check the air handling system for the rack and refer to Trap Details for more information.
TRAP-TYPE    

cpqCmcalarmFan1 153003
The status of Fan 1 has changed. Action: Refer to Trap Details for more information.
TRAP-TYPE    

cpqCmcalarmFan2 153004
The status of Fan 2 has changed. Action: Refer to Trap Details for more information.
TRAP-TYPE    

cpqCmcalarmVoltage 153005
The AC voltage of the rack is outside the specified threshold. Action: Check the incoming power source and ensure all cables are inserted correctly.
TRAP-TYPE    

cpqCmcalarmHumidity 153006
The humidity of the rack is outside the specified threshold. Action: Check the air handling system for the rack and refer to Trap Details for more information.
TRAP-TYPE    

cpqCmcalarmInput1 153007
The door or sidepanel of the rack has been opened (access point #1). Action: Check for unauthorized intrusion and refer to Trap Details for more information.
TRAP-TYPE    

cpqCmcalarmInput2 153008
The door or sidepanel of the rack has been opened (access point #2). Action: Check for unauthorized intrusion and refer to Trap Details for more information.
TRAP-TYPE    

cpqCmcalarmInput3 153009
The door or sidepanel of the rack has been opened (access point #3). Action: Check for unauthorized intrusion and refer to Trap Details for more information.
TRAP-TYPE    

cpqCmcalarmInput4 153010
The door or sidepanel of the rack has been opened (access point #4). Action: Check for unauthorized intrusion and refer to Trap Details for more information.
TRAP-TYPE    

cpqCmcalarmLock1 153011
Rack door lock #1 alarm. Action: Ensure the door is completely closed and check for unauthorized intrusion and refer to Trap Details for more information.
TRAP-TYPE    

cpqCmcalarmLock2 153012
Rack door lock #2 alarm. Action: Ensure the door is completely closed and check for unauthorized intrusion and refer to Trap Details for more information.
TRAP-TYPE    

cpqCmcalarmSmoke 153013
The rack smoke detector has detected smoke. Action: Investigate rack for an over temperature condition and refer to Trap Details for more information.
TRAP-TYPE    

cpqCmcalarmShock 153014
The rack shock detector has detected a vibration to the rack. Action: Investigate rack.
TRAP-TYPE    

cpqCmcalarmAux1 153015
The rack auxiliary alarm input #1 has been triggered.
TRAP-TYPE    

cpqCmcalarmAux2 153016
The rack auxiliary alarm input #2 has been triggered.
TRAP-TYPE    

cpqCmcalarm1 153017
Alarm 1, set from Network management
TRAP-TYPE    

cpqCmcalarm2 153018
Alarm 2, set from Network management
TRAP-TYPE    

cpqCmcalarmLock1Dev 153019
The rack door locking device #1 has failed. Action: Check the device lock cable or failed battery and refer to Trap Details for more information.
TRAP-TYPE    

cpqCmcalarmLock2Dev 153020
The rack door locking device #2 has failed. Action: Check the device lock cable or failed battery and refer to Trap Details for more information.
TRAP-TYPE    

cpqCmcSetupChanged 153100
Setup of CMC has changed.
TRAP-TYPE