CMC-MIB

File: CMC-MIB.mib (45487 bytes)

Imported modules

RFC1155-SMI RFC1213-MIB RFC-1212
RFC-1215

Imported symbols

enterprises DisplayString OBJECT-TYPE
TRAP-TYPE sysDescr sysContact
sysName sysLocation

Defined Types

ValuesEntry  
SEQUENCE    
  valuesIndex INTEGER
  valuesText DisplayString Size(0..31)
  valuesValue INTEGER
  valuesStatus INTEGER
  valuesMaxValue INTEGER
  valuesMinValue INTEGER

StatusEntry  
SEQUENCE    
  statusIndex INTEGER
  statusText DisplayString Size(0..31)
  statusStatus INTEGER

RelayEntry  
SEQUENCE    
  relaytableIndex INTEGER
  relaytableText DisplayString Size(0..31)
  relaytableStatus INTEGER

TrapTableEntry  
SEQUENCE    
  trapIndex INTEGER
  trapStatus INTEGER
  trapIPaddress DisplayString

Defined Values

rittal 1.3.6.1.4.1.2606
OBJECT IDENTIFIER    

cmc 1.3.6.1.4.1.2606.1
OBJECT IDENTIFIER    

values 1.3.6.1.4.1.2606.1.1
OBJECT IDENTIFIER    

table1 1.3.6.1.4.1.2606.1.1.6
OBJECT IDENTIFIER    

status 1.3.6.1.4.1.2606.1.2
OBJECT IDENTIFIER    

table 1.3.6.1.4.1.2606.1.2.18
OBJECT IDENTIFIER    

set 1.3.6.1.4.1.2606.1.3
OBJECT IDENTIFIER    

relayControl 1.3.6.1.4.1.2606.1.3.6
OBJECT IDENTIFIER    

setpoints 1.3.6.1.4.1.2606.1.4
OBJECT IDENTIFIER    

trapControl 1.3.6.1.4.1.2606.1.5
OBJECT IDENTIFIER    

traps 1.3.6.1.4.1.2606.1.5.4
OBJECT IDENTIFIER    

valueTemperature1 1.3.6.1.4.1.2606.1.1.1
Actual value of temperature 1 in deg C
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

valueTemperature2 1.3.6.1.4.1.2606.1.1.2
Actual value of temperature 2 in deg C
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

valuePowerSupply 1.3.6.1.4.1.2606.1.1.3
Actual value of power supply in V
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

valueAnalogAux1 1.3.6.1.4.1.2606.1.1.4
Actual value of aux. analog input 1 (4-20mA = 0-100%)
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

valueAnalogAux2 1.3.6.1.4.1.2606.1.1.5
Actual value of aux. analog input 2 (4-20mA = 0-100%)
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

valuesNumber 1.3.6.1.4.1.2606.1.1.6.1
Number of value-table entries
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

valuesTable 1.3.6.1.4.1.2606.1.1.6.2
Headline of value-table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    ValuesEntry

valuesEntry 1.3.6.1.4.1.2606.1.1.6.2.1
Entries of value-table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  ValuesEntry  

valuesIndex 1.3.6.1.4.1.2606.1.1.6.2.1.1
Index for the list of value entries. Its value ranges between 1 and the value of valuesNumber.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

valuesText 1.3.6.1.4.1.2606.1.1.6.2.1.2
Text of the entry in the value-table
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..31)  

valuesValue 1.3.6.1.4.1.2606.1.1.6.2.1.3
Actual value of the value-table
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

valuesStatus 1.3.6.1.4.1.2606.1.1.6.2.1.4
Status of the value
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER valueOK(1), value-too-low(2), value-too-high(3), valueERROR(4), not-avail(5)  

valuesMaxValue 1.3.6.1.4.1.2606.1.1.6.2.1.5
Value for max. alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

valuesMinValue 1.3.6.1.4.1.2606.1.1.6.2.1.6
Value for min. alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

statusTemperature1 1.3.6.1.4.1.2606.1.2.1
Status temperature 1, OK/ too low/ too high (see setpoints of temperature 1)
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

statusTemperature2 1.3.6.1.4.1.2606.1.2.2
Status temperature 2, OK/ too low/ too high (see setpoints of temperature 2)
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

statusFan1 1.3.6.1.4.1.2606.1.2.3
Status fan 1, Stop/ running/ fault
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

statusFan2 1.3.6.1.4.1.2606.1.2.4
Status fan 2, Stop/ running/ fault
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

statusHeating 1.3.6.1.4.1.2606.1.2.5
Status heating, On/Off
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

statusPowerSupply 1.3.6.1.4.1.2606.1.2.6
Status power supply, OK/ too low/ too high (see setpoints of power supply)
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

statusAnalogAux1 1.3.6.1.4.1.2606.1.2.7
Status aux analog input 1, OK/ too low/ too high
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

statusAnalogAux2 1.3.6.1.4.1.2606.1.2.8
Status aux analog input 2, OK/ too low/ too high
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

statusDoor1 1.3.6.1.4.1.2606.1.2.9
Status door, open/closed/locked
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

statusUps1 1.3.6.1.4.1.2606.1.2.10
Status UPS 1, OK/ fault
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

statusUps2 1.3.6.1.4.1.2606.1.2.11
Status UPS 2, OK/ fault
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

statusSmokeSensor 1.3.6.1.4.1.2606.1.2.12
Status smoke-sensor, OK/ smoke
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

statusVibrationSensor 1.3.6.1.4.1.2606.1.2.13
Status vibration sensor, OK/ vibration
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

statusMessage 1.3.6.1.4.1.2606.1.2.14
Message from CMC
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

valueOperatingTime 1.3.6.1.4.1.2606.1.2.15
Operating time CMC-unit
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

statusUnit 1.3.6.1.4.1.2606.1.2.16
Unit of temperature-values, Celsius or Fahrenheit
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER unitCelsius(1), unitFahrenheit(2)  

statusDoor2 1.3.6.1.4.1.2606.1.2.17
Status door, open/closed/locked
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString Size(0..31)  

statusNumber 1.3.6.1.4.1.2606.1.2.18.1
Number of status-table entries
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

statusTable 1.3.6.1.4.1.2606.1.2.18.2
Headline of table
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    StatusEntry

statusEntry 1.3.6.1.4.1.2606.1.2.18.2.1
A list of status entries. The number of entries is given by the value of statusNumber.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  StatusEntry  

statusIndex 1.3.6.1.4.1.2606.1.2.18.2.1.1
Index fo the list of status entries. Its value ranges between 1 and the value of statusNumber.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

statusText 1.3.6.1.4.1.2606.1.2.18.2.1.2
Text of the entry in the status-table
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..31)  

statusStatus 1.3.6.1.4.1.2606.1.2.18.2.1.3
Status of the table entry
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER statusOK(1), alarm(2), security(3), not-avail(4)  

statusAccess 1.3.6.1.4.1.2606.1.3.1
Status access
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..31)  

setDoor1 1.3.6.1.4.1.2606.1.3.2
Set door, see table
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER lockDoor(1), openDoorTime(2), openDoorAccess(3), openDoor(4)  

setMessage 1.3.6.1.4.1.2606.1.3.3
Set message
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..31)  

setFault 1.3.6.1.4.1.2606.1.3.4
Set fault, see table
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER clearFault(1), setFault(2)  

setDoor2 1.3.6.1.4.1.2606.1.3.5
Set door, see table
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER lockDoor(1), openDoorTime(2), openDoorAccess(3), openDoor(4)  

relaytableMaxNum 1.3.6.1.4.1.2606.1.3.6.1
Number of table entries
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

relayTable 1.3.6.1.4.1.2606.1.3.6.2
Headline of table for relay control
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    RelayEntry

relayEntry 1.3.6.1.4.1.2606.1.3.6.2.1
Entries
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  RelayEntry  

relaytableIndex 1.3.6.1.4.1.2606.1.3.6.2.1.1
Index for the relay-table. Its value ranges between 1 and relaytableMaxNum
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

relaytableText 1.3.6.1.4.1.2606.1.3.6.2.1.2
Description-Text for each relay in the table
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..31)  

relaytableStatus 1.3.6.1.4.1.2606.1.3.6.2.1.3
Status of relays in the table
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER relayOFF(1), relayON(2), not-avail(3)  

setpointFan1 1.3.6.1.4.1.2606.1.4.1
Setpoint Fan 1 in C, Fan 1 will start if temperature 1 exceeds this value
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

setpointFan2 1.3.6.1.4.1.2606.1.4.2
Setpoint Fan 2 in C, Fan 2 will start if temperature 2 exceeds this value
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

setpointHeating 1.3.6.1.4.1.2606.1.4.3
Setpoint heating in C, heating will start if lowest value of temperature 1 and 2 falls below this value
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

setpointHighTemperature1 1.3.6.1.4.1.2606.1.4.4
Setpoint high value alarm temperature 1
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

setpointLowTemperature1 1.3.6.1.4.1.2606.1.4.5
Setpoint low value alarm temperature 1
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

setpointHighTemperature2 1.3.6.1.4.1.2606.1.4.6
Setpoint high value alarm temperature 2
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

setpointLowTemperature2 1.3.6.1.4.1.2606.1.4.7
Setpoint low value alarm temperature 2
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

setpointHighVoltage 1.3.6.1.4.1.2606.1.4.8
Setpoint high value supply voltage alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

setpointLowVoltage 1.3.6.1.4.1.2606.1.4.9
Setpoint low value supply voltage alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

setpointLowAux1 1.3.6.1.4.1.2606.1.4.10
Setpoint low value Aux input 1 alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

setpointHighAux1 1.3.6.1.4.1.2606.1.4.11
Setpoint high value Aux input 1 alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

setpointLowAux2 1.3.6.1.4.1.2606.1.4.12
Setpoint low value Aux input 2 alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

setpointHighAux2 1.3.6.1.4.1.2606.1.4.13
Setpoint high value Aux input alarm
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

setTrapRepeat 1.3.6.1.4.1.2606.1.5.1
Enable/disable repeating of traps. If enabled, traps will be repeated after a repeat time, set in setTrapRepeatTime. Repeating can be stopped by setting setTrapQuit to quitTrap
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disableTrapRepeat(1), enableTrapRepeat(2)  

setTrapRepeatTime 1.3.6.1.4.1.2606.1.5.2
Time value (sec) for trap-repeating, if setTrapRepeat is enabled
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER  

setTrapQuit 1.3.6.1.4.1.2606.1.5.3
Quit trap to stop repeating.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER quitTrap(1), quitTrapOK(2), noTrapToQuit(3), trapToQuit(4)  

traptableNumber 1.3.6.1.4.1.2606.1.5.4.1
Number of trapTable entries. The number of trap-receiver
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

trapTable 1.3.6.1.4.1.2606.1.5.4.2
A list of trap-receiver entries
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    TrapTableEntry

trapTableEntry 1.3.6.1.4.1.2606.1.5.4.2.1
Entries of trapTable
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  TrapTableEntry  

trapIndex 1.3.6.1.4.1.2606.1.5.4.2.1.1
Index for the trap-receiver-table. Its value ranges between 1 and the value of traptableNumber
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

trapStatus 1.3.6.1.4.1.2606.1.5.4.2.1.2
Enable or disable trap receiver
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER enabled(1), disabled(2)  

trapIPaddress 1.3.6.1.4.1.2606.1.5.4.2.1.3
IP-address of trap-receiver
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..31)  

alarmTemperature1 1
Alarm temperature 1, temperature 1 exceeds high-setpoint or falls below low-setpoint of temperature 1
TRAP-TYPE    

alarmTemperature2 2
Alarm temperature 2, temperature 2 exceeds high-setpoint or falls below low-setpoint of temperature 2
TRAP-TYPE    

alarmFan1 3
Alarm fan 1, no current to fan 1
TRAP-TYPE    

alarmFan2 4
Alarm fan 2, no current to fan 2
TRAP-TYPE    

alarmVoltage 5
Alarm supply-voltage, voltage exceeds high-setpoint or falls below low-setpoint of supply-voltage
TRAP-TYPE    

alarmSmoke 6
Alarm smoke-sensor
TRAP-TYPE    

alarmVibration 7
Alarm vibration-sensor
TRAP-TYPE    

alarmUPS1 8
Alarm UPS1
TRAP-TYPE    

alarmUPS2 9
Alarm UPS2
TRAP-TYPE    

alarmDoor 10
Alarm Door/Door lock
TRAP-TYPE    

alarmAnalogAux1 11
Alarm Analog Input Aux1 (4-20mA), value not OK
TRAP-TYPE    

alarmAnalogAux2 12
Alarm Analog Input Aux2 (4-20mA), value not OK
TRAP-TYPE    

msgAccess 13
Access message
TRAP-TYPE    

okTrap 14
Trap for OK- message. This trap is send, if a detected alarm is gone
TRAP-TYPE    

alarm1 21
Trap 1
TRAP-TYPE    

alarm2 22
Trap 2
TRAP-TYPE    

alarm3 23
Trap 3
TRAP-TYPE    

alarm4 24
Trap 4
TRAP-TYPE    

alarm5 25
Trap 5
TRAP-TYPE    

alarm6 26
Trap 6
TRAP-TYPE    

alarm7 27
Trap 7
TRAP-TYPE    

alarm8 28
Trap 8
TRAP-TYPE    

alarm9 29
Trap 9
TRAP-TYPE    

alarm10 30
Trap 10
TRAP-TYPE    

alarm11 31
Trap 11
TRAP-TYPE    

alarm12 32
Trap 12
TRAP-TYPE    

alarm13 33
Trap 13
TRAP-TYPE    

alarm14 34
Trap 14
TRAP-TYPE    

alarm15 35
Trap 15
TRAP-TYPE    

alarm16 36
Trap 16
TRAP-TYPE    

alarm17 37
Trap 17
TRAP-TYPE    

alarm18 38
Trap 18
TRAP-TYPE    

alarm19 39
Trap 19
TRAP-TYPE    

alarm20 40
Trap 20
TRAP-TYPE    

alarm21 41
Trap 21
TRAP-TYPE    

alarm22 42
Trap 22
TRAP-TYPE    

alarm23 43
Trap 23
TRAP-TYPE    

alarm24 44
Trap 24
TRAP-TYPE    

alarm25 45
Trap 25
TRAP-TYPE    

alarm26 46
Trap 26
TRAP-TYPE    

alarm27 47
Trap 27
TRAP-TYPE    

alarm28 48
Trap 28
TRAP-TYPE    

alarm29 49
Trap 29
TRAP-TYPE    

alarm30 50
Trap 30
TRAP-TYPE    

alarm31 51
Trap 31
TRAP-TYPE    

alarm32 52
Trap 32
TRAP-TYPE    

alarm33 53
Trap 33
TRAP-TYPE    

alarm34 54
Trap 34
TRAP-TYPE    

alarm35 55
Trap 35
TRAP-TYPE