Argus-Power-System-MIB
File:
Argus-Power-System-MIB.mib (24073 bytes)
Imported modules
Imported symbols
Defined Types
PositiveInteger |
|
This data type is a non-zero and non-negative value. |
TEXTUAL-CONVENTION |
|
|
|
|
INTEGER |
1..2147483647 |
|
NonNegativeInteger |
|
This data type is a non-negative value. |
TEXTUAL-CONVENTION |
|
|
|
|
INTEGER |
0..2147483647 |
|
UpsInputEntry |
|
SEQUENCE |
|
|
|
|
upsInputLineIndex |
INTEGER |
|
|
upsInputFrequency |
INTEGER |
|
|
upsInputVoltage |
INTEGER |
|
UpsOutputEntry |
|
SEQUENCE |
|
|
|
|
upsOutputLineIndex |
INTEGER |
|
|
upsOutputVoltage |
INTEGER |
|
|
upsOutputCurrent |
INTEGER |
|
|
upsOutputPowerVA |
INTEGER |
|
|
upsOutputPowerWatt |
INTEGER |
|
|
upsPowerFactor |
INTEGER |
|
|
upsOutputPercentLoad |
INTEGER |
|
UpsAlarmEntry |
|
SEQUENCE |
|
|
|
|
upsAlarmId |
INTEGER |
|
|
upsAlarmDescr |
DisplayString |
|
|
upsAlarmStatus |
INTEGER |
|
Defined Values
argus |
1.3.6.1.4.1.7309 |
This MIB defines the information block(s) available in CXC RMU
as defined by the following list:
- upsDevice: the CXC-series of controllers |
MODULE-IDENTITY |
|
|
|
upsPower |
1.3.6.1.4.1.7309.6 |
OBJECT IDENTIFIER |
|
|
|
upsDevice |
1.3.6.1.4.1.7309.6.1 |
OBJECT IDENTIFIER |
|
|
|
upsIdent |
1.3.6.1.4.1.7309.6.1.1 |
OBJECT IDENTIFIER |
|
|
|
upsBattery |
1.3.6.1.4.1.7309.6.1.2 |
OBJECT IDENTIFIER |
|
|
|
upsOutput |
1.3.6.1.4.1.7309.6.1.4 |
OBJECT IDENTIFIER |
|
|
|
upsAlarm |
1.3.6.1.4.1.7309.6.1.5 |
OBJECT IDENTIFIER |
|
|
|
upsConfig |
1.3.6.1.4.1.7309.6.1.6 |
OBJECT IDENTIFIER |
|
|
|
upsTraps |
1.3.6.1.4.1.7309.6.1.7 |
OBJECT IDENTIFIER |
|
|
|
upsTrap |
1.3.6.1.4.1.7309.6.1.7.0 |
OBJECT IDENTIFIER |
|
|
|
upsAlarmTrap |
1.3.6.1.4.1.7309.6.1.7.0.1 |
A trap issued from a change in state in one of the Alarms on the Novus controller |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
upsAgentStartupTrap |
1.3.6.1.4.1.7309.6.1.7.0.2 |
A trap to indicate that the agent software has started up. |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
upsAgentShutdownTrap |
1.3.6.1.4.1.7309.6.1.7.0.3 |
A trap to indicate that the agent software has shutdown. |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
upsAgentFaultTrap |
1.3.6.1.4.1.7309.6.1.7.0.4 |
A trap issued from a change in state in one of the Faults on the Novus controller |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
upsAgentEventTrap |
1.3.6.1.4.1.7309.6.1.7.0.5 |
A trap issued from a change in state in one of the Events on the Novus controller |
Status: current |
Access: read-only |
NOTIFICATION-TYPE |
|
|
|
upsIdentModel |
1.3.6.1.4.1.7309.6.1.1.3 |
The UPS Product code designation. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..255) |
|
upsIdentUPSSoftwareVersion |
1.3.6.1.4.1.7309.6.1.1.4 |
The UPS firmware/software version(s). This variable
may or may not have the same value as
upsIdentAgentSoftwareVersion in some implementations. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..255) |
|
upsIdentAgentSoftwareVersion |
1.3.6.1.4.1.7309.6.1.1.5 |
The UPS agent software version. This variable may or
may not have the same value as
upsIdentUPSSoftwareVersion in some implementations. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..255) |
|
upsIdentName |
1.3.6.1.4.1.7309.6.1.1.6 |
A string identifying the UPS. This object should be
set by the administrator. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..255) |
|
upsIdentAttachedDevices |
1.3.6.1.4.1.7309.6.1.1.7 |
A string identifying the devices attached to the
output(s) of the UPS. This object should be set by
the administrator. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..255) |
|
upsIdentDate |
1.3.6.1.4.1.7309.6.1.1.14 |
Date of the RMU-Novus |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..255) |
|
upsIdentTime |
1.3.6.1.4.1.7309.6.1.1.15 |
Time of the RMU-Novus |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..255) |
|
upsBatteryStatus |
1.3.6.1.4.1.7309.6.1.2.1 |
The indication of the capacity remaining in the UPS
system's batteries. A value of batteryNormal
indicates that the remaining run-time is greater than
upsConfigLowBattTime. A value of batteryLow indicates
that the remaining battery run-time is less than or
equal to upsConfigLowBattTime. A value of
batteryDepleted indicates that the UPS will be unable
to sustain the present load when and if the utility
power is lost (including the possibility that the
utility power is currently absent and the UPS is
unable to sustain the output). |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
unknown(1), batteryNormal(2), batteryLow(3), batteryDepleted(4) |
|
upsMinutesOnBattery |
1.3.6.1.4.1.7309.6.1.2.2 |
The accumulated elapsed time that the UPS system have been on battery.
|
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsBatteryVoltage |
1.3.6.1.4.1.7309.6.1.2.3 |
The magnitude of the present battery voltage. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsBatteryChargingCurrent |
1.3.6.1.4.1.7309.6.1.2.4 |
The present battery charging current. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsBatteryCapacity |
1.3.6.1.4.1.7309.6.1.2.5 |
The present battery capacity. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsBatteryTemperature |
1.3.6.1.4.1.7309.6.1.2.6 |
The ambient temperature at or near the UPS Battery
casing. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsBatteryLowWarning |
1.3.6.1.4.1.7309.6.1.2.7 |
The set battery capacity percentage at which the unit will raise an alarm. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsInputEntry |
1.3.6.1.4.1.7309.6.1.3.2.1 |
An entry containing information applicable to a
particular input line. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
UpsInputEntry |
|
|
upsOutputSource |
1.3.6.1.4.1.7309.6.1.4.1 |
The present source of output power. The enumeration
line(2) indicates that the Novus is in line mode. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
standby(1), line(2), boost2(3), boost1(4), buck1(5), buck2(6), inverter(7), retransfer(8), transfer(9), shutdown(10), bypass(11) |
|
upsOutputFrequency |
1.3.6.1.4.1.7309.6.1.4.2 |
The present output frequency. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsOutputNumLines |
1.3.6.1.4.1.7309.6.1.4.3 |
The number of output lines utilized in this device.
This variable indicates the number of rows in the
output table. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsOutputTable |
1.3.6.1.4.1.7309.6.1.4.4 |
A list of output table entries. The number of
entries is given by the value of upsOutputNumLines. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
UpsOutputEntry |
|
upsOutputEntry |
1.3.6.1.4.1.7309.6.1.4.4.1 |
An entry containing information applicable to a
particular output line. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
UpsOutputEntry |
|
|
upsOutputLineIndex |
1.3.6.1.4.1.7309.6.1.4.4.1.1 |
The output line identifier. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsOutputVoltage |
1.3.6.1.4.1.7309.6.1.4.4.1.2 |
The present output voltage. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsOutputCurrent |
1.3.6.1.4.1.7309.6.1.4.4.1.3 |
The present output current. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsOutputPowerVA |
1.3.6.1.4.1.7309.6.1.4.4.1.4 |
The present output VA. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsOutputPowerWatt |
1.3.6.1.4.1.7309.6.1.4.4.1.5 |
The present output true power. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsPowerFactor |
1.3.6.1.4.1.7309.6.1.4.4.1.6 |
The present power factor. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsOutputPercentLoad |
1.3.6.1.4.1.7309.6.1.4.4.1.7 |
The percentage of the UPS power capacity presently
being used on this output line, i.e., the greater of
the percent load of true power capacity and the
percent load of VA. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..200 |
|
upsAlarmsPresent |
1.3.6.1.4.1.7309.6.1.5.1 |
The present number of active alarm conditions. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmTable |
1.3.6.1.4.1.7309.6.1.5.2 |
A list of alarm table entries. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
UpsAlarmEntry |
|
upsAlarmEntry |
1.3.6.1.4.1.7309.6.1.5.2.1 |
An entry containing information applicable to a
particular alarm. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
UpsAlarmEntry |
|
|
upsAlarmId |
1.3.6.1.4.1.7309.6.1.5.2.1.1 |
A unique identifier for an alarm condition. This
value must remain constant. |
Status: current |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsAlarmDescr |
1.3.6.1.4.1.7309.6.1.5.2.1.2 |
A unique description of the alarm. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..255) |
|
upsAlarmStatus |
1.3.6.1.4.1.7309.6.1.5.2.1.3 |
1 - ON or 0 - OFF. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsConfigLineQualifyTime |
1.3.6.1.4.1.7309.6.1.6.1 |
This objects displays the line qualify time. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsConfigLineOutputVoltageLowLimit |
1.3.6.1.4.1.7309.6.1.6.3 |
This object represents the Line output Low Voltage Limit. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsConfigFanOnTemperature |
1.3.6.1.4.1.7309.6.1.6.4 |
This object represents the Fan on temperature. |
Status: current |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsShutdownStatus |
1.3.6.1.4.1.7309.6.1.6.5 |
This object tells us if output is disabled or enabled. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsInverterOffDelayTime |
1.3.6.1.4.1.7309.6.1.6.6 |
This object represents the inverter off delay time. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
upsConfigIPAddress |
1.3.6.1.4.1.7309.6.1.6.7 |
This objects displays the IP address of the RMU. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..255) |
|
upsConfigNetMask |
1.3.6.1.4.1.7309.6.1.6.8 |
This object displays the Net Mask of the RMU. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..255) |
|
upsConfigGateway |
1.3.6.1.4.1.7309.6.1.6.9 |
This object displays the Gateway of the RMU. |
Status: current |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
Size(0..255) |
|