ASETEK-RACKCDU-SMI-V1-MIB-V16
File:
ASETEK-RACKCDU-SMI-V1-MIB-V16.mib (59251 bytes)
Imported modules
Imported symbols
Defined Types
NotifyEntry |
|
SEQUENCE |
|
|
|
|
notifyReceiverNumber |
INTEGER |
|
|
notifyEnabled |
INTEGER |
|
|
notifyReceiverIPAddress |
IpAddress |
|
|
notifyCommunity |
DisplayString |
|
Defined Values
asetek |
1.3.6.1.4.1.39829 |
OBJECT IDENTIFIER |
|
|
|
rackCDU |
1.3.6.1.4.1.39829.1 |
OBJECT IDENTIFIER |
|
|
|
traps |
1.3.6.1.4.1.39829.1.0 |
OBJECT IDENTIFIER |
|
|
|
product |
1.3.6.1.4.1.39829.1.1 |
OBJECT IDENTIFIER |
|
|
|
name |
1.3.6.1.4.1.39829.1.1.1 |
Product name. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
version |
1.3.6.1.4.1.39829.1.1.2 |
Software version. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
date |
1.3.6.1.4.1.39829.1.1.3 |
Software revision date. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
status |
1.3.6.1.4.1.39829.1.1.6 |
The overall status of the RackCDU. Status is evaluated based on the
notification settings. If a noticiation has been disabled it will not
be included in the overall status either. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
ok(1), warning(2), error(3), unknown(5) |
|
setup |
1.3.6.1.4.1.39829.1.2 |
OBJECT IDENTIFIER |
|
|
|
notifyTable |
1.3.6.1.4.1.39829.1.2.1 |
Table of settings used to setup notifications. |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
SEQUENCE OF |
|
|
|
|
NotifyEntry |
|
notifyEntry |
1.3.6.1.4.1.39829.1.2.1.1 |
Single notify entry containing notification receiver info. |
Status: mandatory |
Access: not-accessible |
OBJECT-TYPE |
|
|
|
|
NotifyEntry |
|
|
notifyReceiverNumber |
1.3.6.1.4.1.39829.1.2.1.1.1 |
Index of notification receiver. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..4 |
|
notifyEnabled |
1.3.6.1.4.1.39829.1.2.1.1.2 |
Indicates if this notify entry is enabled or not. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
no(1), yes(2) |
|
temperatureFacilityIn |
1.3.6.1.4.1.39829.1.3.100 |
The temperature of the water going into the RackCDU on the Facility side
(cold). |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-870..999 |
|
temperatureFacilityOut |
1.3.6.1.4.1.39829.1.3.101 |
The temperature of the water going out of the RackCDU on the Facility
side (hot). |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-870..999 |
|
temperatureServerIn |
1.3.6.1.4.1.39829.1.3.102 |
The temperature of the water going into the servers node (cold). |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-870..999 |
|
temperatureServerOut |
1.3.6.1.4.1.39829.1.3.103 |
The temperature of the water going out of the servers node (hot). |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-870..999 |
|
temperatureAmbient |
1.3.6.1.4.1.39829.1.3.104 |
The temperature of the ambient air close to the RackCDU. |
Status: obsolete |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-870..999 |
|
pressureServer |
1.3.6.1.4.1.39829.1.3.105 |
The pressure inside the RackCDU on the server side. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Gauge |
|
|
pressureFacility |
1.3.6.1.4.1.39829.1.3.106 |
The pressure inside the RackCDU on the facility side. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Gauge |
|
|
serverLeak |
1.3.6.1.4.1.39829.1.3.107 |
Boolean indication of whether the RackCDU has detected a leak in the
system. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
ok(1), leak(2) |
|
serverLevel |
1.3.6.1.4.1.39829.1.3.108 |
Boolean indication of whether the RackCDU has detected a low level of
cooleant. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
ok(1), low(2) |
|
flowFacility |
1.3.6.1.4.1.39829.1.3.109 |
The flow of the cooleant on the facility side. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Gauge |
|
|
heatload |
1.3.6.1.4.1.39829.1.3.110 |
The heatload of the cooleant on the facility side. Can be averaged from
e.g. 1 to 28800 (24 hours) sec. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Gauge |
|
|
controllerOut |
1.3.6.1.4.1.39829.1.3.111 |
The controller output. |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
Gauge |
|
|
network |
1.3.6.1.4.1.39829.1.4 |
OBJECT IDENTIFIER |
|
|
|
ipStoreFlash |
1.3.6.1.4.1.39829.1.4.91 |
store settings to Flash. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(1), store(2) |
|
modeOfOperation |
1.3.6.1.4.1.39829.1.4.92 |
Mode of operation of ControlBox, can be agent or master. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
agent(1), master(2) |
|
ipAddr |
1.3.6.1.4.1.39829.1.4.93 |
IP address of ControlBox. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
IpAddress |
|
|
priDNS |
1.3.6.1.4.1.39829.1.4.94 |
Primary DNS address of ControlBox. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
IpAddress |
|
|
secDNS |
1.3.6.1.4.1.39829.1.4.95 |
Secondary DNS address of ControlBox. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
IpAddress |
|
|
netMask |
1.3.6.1.4.1.39829.1.4.96 |
Netmask of ControlBox. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
IpAddress |
|
|
gateway |
1.3.6.1.4.1.39829.1.4.97 |
Gateway of ControlBox. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
IpAddress |
|
|
ipSrc |
1.3.6.1.4.1.39829.1.4.98 |
IP address source of ControlBox, eg. static or dhcp. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
static(1), dhcp(2) |
|
ipReboot |
1.3.6.1.4.1.39829.1.4.99 |
IP address reboot. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
normal(1), reboot(2) |
|
controller |
1.3.6.1.4.1.39829.1.5 |
OBJECT IDENTIFIER |
|
|
|
gainIntegral |
1.3.6.1.4.1.39829.1.5.81 |
Integral gain in PID controller. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
deltaOutMax |
1.3.6.1.4.1.39829.1.5.83 |
Maximum delta output from controller. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Gauge |
|
|
limitPwmMax |
1.3.6.1.4.1.39829.1.5.84 |
Maximum PWM output. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Gauge |
|
|
limitPwmMin |
1.3.6.1.4.1.39829.1.5.85 |
Minimum PWM output. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Gauge |
|
|
setpointFacilityOut |
1.3.6.1.4.1.39829.1.5.86 |
Setpoint for Facility Out Temperature. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..100 |
|
controllerOutAlpha |
1.3.6.1.4.1.39829.1.5.87 |
Controller Out Alpha - damping factor of output. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
units |
1.3.6.1.4.1.39829.1.6 |
OBJECT IDENTIFIER |
|
|
|
fluidHeatCapacity |
1.3.6.1.4.1.39829.1.6.70 |
Heat Capacity of the liquid coolant utilized in the facility loop. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..65000 |
|
heatAverageFactor |
1.3.6.1.4.1.39829.1.6.71 |
The time frame of which the heat load is averaged. A short time frame
make the heat load sensative to small changes is temperature and flow
which results in a highly fluctuating value. A long time frame
stabilizes the value, but also results in a long response time. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Gauge |
|
|
harnessVersion |
1.3.6.1.4.1.39829.1.6.72 |
Must be set to the harness version utilized by the RackCDU. The harness
version may affect the functionality of the RackCDU and it it therefor
important that the versions is matched. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
Gauge |
|
|
snmpTrapsAlarmEnable |
1.3.6.1.4.1.39829.1.7.150 |
Enable SNMP Alarm traps. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(1), enabled(2) |
|
snmpTrapsWarningEnable |
1.3.6.1.4.1.39829.1.7.151 |
Enable SNMP Warning traps. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(1), enabled(2) |
|
smtpTrapsAlarmEnable |
1.3.6.1.4.1.39829.1.7.152 |
Enable SMTP Alarm traps. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(1), enabled(2) |
|
smtpTrapsWarningEnable |
1.3.6.1.4.1.39829.1.7.153 |
Enable SMTP Warning traps. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(1), enabled(2) |
|
warningMinFi |
1.3.6.1.4.1.39829.1.7.154 |
Set Facility In Min Warning level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-75..75 |
|
warningMinEnableFi |
1.3.6.1.4.1.39829.1.7.155 |
Enable Facility In Min Warning level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(1), enabled(2) |
|
warningMaxFi |
1.3.6.1.4.1.39829.1.7.156 |
Set Facility In Max Warning level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-75..75 |
|
warningMaxEnableFi |
1.3.6.1.4.1.39829.1.7.157 |
Enable Facility In Max Warning level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(1), enabled(2) |
|
alarmMinFi |
1.3.6.1.4.1.39829.1.7.158 |
Set Facility In Min Alarm level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-75..75 |
|
alarmMinEnableFi |
1.3.6.1.4.1.39829.1.7.159 |
Enable Facility In Min Alarm level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(1), enabled(2) |
|
alarmMaxFi |
1.3.6.1.4.1.39829.1.7.160 |
Set Facility In Max Alarm level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-75..75 |
|
alarmMaxEnableFi |
1.3.6.1.4.1.39829.1.7.161 |
Enable Facility In Max Alarm level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(1), enabled(2) |
|
warningMinFo |
1.3.6.1.4.1.39829.1.7.162 |
Set Facility Out Min Warning level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-75..75 |
|
warningMinEnableFo |
1.3.6.1.4.1.39829.1.7.163 |
Enable Facility Out Min Warning level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(1), enabled(2) |
|
warningMaxFo |
1.3.6.1.4.1.39829.1.7.164 |
Set Facility Out Max Warning level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-75..75 |
|
warningMaxEnableFo |
1.3.6.1.4.1.39829.1.7.165 |
Enable Facility Out Max Warning level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(1), enabled(2) |
|
alarmMinFo |
1.3.6.1.4.1.39829.1.7.166 |
Set Facility Out Min alarm level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-75..75 |
|
alarmMinEnableFo |
1.3.6.1.4.1.39829.1.7.167 |
Enable Facility Out Min alarm level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(1), enabled(2) |
|
alarmMaxFo |
1.3.6.1.4.1.39829.1.7.168 |
Set Facility Out Max Alarm level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-75..75 |
|
alarmMaxEnableFo |
1.3.6.1.4.1.39829.1.7.169 |
Enable Facility Out Max Alarm level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(1), enabled(2) |
|
warningMinSi |
1.3.6.1.4.1.39829.1.7.170 |
Set Server In Min Warning level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-75..75 |
|
warningMinEnableSi |
1.3.6.1.4.1.39829.1.7.171 |
Enable Server In Min Warning level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(1), enabled(2) |
|
warningMaxSi |
1.3.6.1.4.1.39829.1.7.172 |
Set Server In Max Warning level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-75..75 |
|
warningMaxEnableSi |
1.3.6.1.4.1.39829.1.7.173 |
Enable Server In Max Warning level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(1), enabled(2) |
|
alarmMinSi |
1.3.6.1.4.1.39829.1.7.174 |
Set Server In Min Alarm level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-75..75 |
|
alarmMinEnableSi |
1.3.6.1.4.1.39829.1.7.175 |
Enable Server In Min Alarm level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(1), enabled(2) |
|
alarmMaxSi |
1.3.6.1.4.1.39829.1.7.176 |
Set Server In Max Alarm level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-75..75 |
|
alarmMaxEnableSi |
1.3.6.1.4.1.39829.1.7.177 |
Enable Server In Max Alarm level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(1), enabled(2) |
|
warningMinSo |
1.3.6.1.4.1.39829.1.7.178 |
Set Server Out Min Warning level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-75..75 |
|
warningMinEnableSo |
1.3.6.1.4.1.39829.1.7.179 |
Enable Server Out Min Warning level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(1), enabled(2) |
|
warningMaxSo |
1.3.6.1.4.1.39829.1.7.180 |
Set Server Out Max Warning level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-75..75 |
|
warningMaxEnableSo |
1.3.6.1.4.1.39829.1.7.181 |
Enable Server Out Max Warning level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(1), enabled(2) |
|
alarmMinSo |
1.3.6.1.4.1.39829.1.7.182 |
Set Server Out Min Alarm level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-75..75 |
|
alarmMinEnableSo |
1.3.6.1.4.1.39829.1.7.183 |
Enable Server Out Min Alarm level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(1), enabled(2) |
|
alarmMaxSo |
1.3.6.1.4.1.39829.1.7.184 |
Set Server Out Max Alarm level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
-75..75 |
|
alarmMaxEnableSo |
1.3.6.1.4.1.39829.1.7.185 |
Enable Server Out Max Alarm level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(1), enabled(2) |
|
warningMinFlow |
1.3.6.1.4.1.39829.1.7.186 |
Set Flow Min Warning level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..3500000 |
|
warningMinEnableFlow |
1.3.6.1.4.1.39829.1.7.187 |
Enable Flow Min Warning level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(1), enabled(2) |
|
warningMaxFlow |
1.3.6.1.4.1.39829.1.7.188 |
Set Flow Max Warning level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..3500000 |
|
warningMaxEnableFlow |
1.3.6.1.4.1.39829.1.7.189 |
Enable Flow Max Warning level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(1), enabled(2) |
|
alarmMinFlow |
1.3.6.1.4.1.39829.1.7.190 |
Set Flow Min Alarm level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..3500000 |
|
alarmMinEnableFlow |
1.3.6.1.4.1.39829.1.7.191 |
Enable Flow Min Alarm level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(1), enabled(2) |
|
alarmMaxFlow |
1.3.6.1.4.1.39829.1.7.192 |
Set Flow Max Alarm level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..3500000 |
|
alarmMaxEnableFlow |
1.3.6.1.4.1.39829.1.7.193 |
Enable Flow Max Alarm level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(1), enabled(2) |
|
warningMinPressureServer |
1.3.6.1.4.1.39829.1.7.194 |
Set Server Pressure Min Warning level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..3500 |
|
warningMinEnablePressureServer |
1.3.6.1.4.1.39829.1.7.195 |
Enable Server Pressure Min Warning level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(1), enabled(2) |
|
warningMaxPressureServer |
1.3.6.1.4.1.39829.1.7.196 |
Set Server Pressure Max Warning level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..3500 |
|
warningMaxEnablePressureServer |
1.3.6.1.4.1.39829.1.7.197 |
Enable Server Pressure Max Warning level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(1), enabled(2) |
|
alarmMinPressureServer |
1.3.6.1.4.1.39829.1.7.198 |
Set Server Pressure Min Alarm level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..3500 |
|
alarmMinEnablePressureServer |
1.3.6.1.4.1.39829.1.7.199 |
Enable Server Pressure Min Alarm level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(1), enabled(2) |
|
alarmMaxPressureServer |
1.3.6.1.4.1.39829.1.7.200 |
Set Server Pressure Max Alarm level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..3500 |
|
alarmMaxEnablePressureServer |
1.3.6.1.4.1.39829.1.7.201 |
Enable Server Pressure Max Alarm level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(1), enabled(2) |
|
warningMinPressureFacility |
1.3.6.1.4.1.39829.1.7.202 |
Set Facility Pressure Min Warning level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..3500 |
|
warningMinEnablePressureFacility |
1.3.6.1.4.1.39829.1.7.203 |
Enable Facility Pressure Min Warning level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(1), enabled(2) |
|
warningMaxPressureFacility |
1.3.6.1.4.1.39829.1.7.204 |
Set Facility Pressure Max Warning level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..3500 |
|
warningMaxEnablePressureFacility |
1.3.6.1.4.1.39829.1.7.205 |
Enable Facility Pressure Max Warning level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(1), enabled(2) |
|
alarmMinPressureFacility |
1.3.6.1.4.1.39829.1.7.206 |
Set Facility Pressure Min Alarm level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..3500 |
|
alarmMinEnablePressureFacility |
1.3.6.1.4.1.39829.1.7.207 |
Enable Facility Pressure Min Alarm level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(1), enabled(2) |
|
alarmMaxPressureFacility |
1.3.6.1.4.1.39829.1.7.208 |
Set Facility Pressure Max Alarm level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
0..3500 |
|
alarmMaxEnablePressureFacility |
1.3.6.1.4.1.39829.1.7.209 |
Enable Facility Pressure Max Alarm level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(1), enabled(2) |
|
alarmEnableLeak |
1.3.6.1.4.1.39829.1.7.210 |
Enable leak detection. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(1), enabled(2) |
|
alarmEnableLevel |
1.3.6.1.4.1.39829.1.7.211 |
Enable low liquid level. |
Status: mandatory |
Access: read-write |
OBJECT-TYPE |
|
|
|
|
INTEGER |
disabled(1), enabled(2) |
|
eventDescription |
1.3.6.1.4.1.39829.1.9.1 |
Text which provide the user with a corrective action in case of a
warning or alarm trap.
IMPORTANT: Must only be used in traps! Any other use of this object is
invalid.
|
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
DisplayString |
|
|
eventValue |
1.3.6.1.4.1.39829.1.9.2 |
Event value placeholder sent with generic traps where the unit of the
value can be different.
IMPORTANT: Must only be used in traps! Any other use of this object is
invalid |
Status: mandatory |
Access: read-only |
OBJECT-TYPE |
|
|
|
|
INTEGER |
|
|
alarmNotify |
500 |
Trap alarm notification information for the SNMP Manager (obsolete). |
TRAP-TYPE |
|
|
|
warningNotify |
501 |
Trap warning notification information for the SNMP Manager (obsolete). |
TRAP-TYPE |
|
|
|