ASETEK-RACKCDU-SMI-V1-MIB-V16

File: ASETEK-RACKCDU-SMI-V1-MIB-V16.mib (59251 bytes)

Imported modules

RFC-1212 RFC-1215 RFC1155-SMI
RFC1213-MIB

Imported symbols

OBJECT-TYPE TRAP-TYPE enterprises
IpAddress Gauge sysDescr
sysObjectID sysUpTime sysContact
sysName sysLocation sysServices
DisplayString

Defined Types

NotifyEntry  
SEQUENCE    
  notifyReceiverNumber INTEGER
  notifyEnabled INTEGER
  notifyReceiverIPAddress IpAddress
  notifyCommunity DisplayString

Defined Values

asetek 1.3.6.1.4.1.39829
OBJECT IDENTIFIER    

rackCDU 1.3.6.1.4.1.39829.1
OBJECT IDENTIFIER    

traps 1.3.6.1.4.1.39829.1.0
OBJECT IDENTIFIER    

product 1.3.6.1.4.1.39829.1.1
OBJECT IDENTIFIER    

name 1.3.6.1.4.1.39829.1.1.1
Product name.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

version 1.3.6.1.4.1.39829.1.1.2
Software version.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

date 1.3.6.1.4.1.39829.1.1.3
Software revision date.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

rackNumber 1.3.6.1.4.1.39829.1.1.4
RackCDU number.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

description 1.3.6.1.4.1.39829.1.1.5
RackCDU description.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

status 1.3.6.1.4.1.39829.1.1.6
The overall status of the RackCDU. Status is evaluated based on the notification settings. If a noticiation has been disabled it will not be included in the overall status either.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER ok(1), warning(2), error(3), unknown(5)  

setup 1.3.6.1.4.1.39829.1.2
OBJECT IDENTIFIER    

notifyTable 1.3.6.1.4.1.39829.1.2.1
Table of settings used to setup notifications.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    NotifyEntry

notifyEntry 1.3.6.1.4.1.39829.1.2.1.1
Single notify entry containing notification receiver info.
Status: mandatory Access: not-accessible
OBJECT-TYPE    
  NotifyEntry  

notifyReceiverNumber 1.3.6.1.4.1.39829.1.2.1.1.1
Index of notification receiver.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER 0..4  

notifyEnabled 1.3.6.1.4.1.39829.1.2.1.1.2
Indicates if this notify entry is enabled or not.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER no(1), yes(2)  

notifyReceiverIPAddress 1.3.6.1.4.1.39829.1.2.1.1.3
Notification receiver IP address.
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

notifyCommunity 1.3.6.1.4.1.39829.1.2.1.1.4
Notification community to be used by agent to send trap.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString Size(0..7)  

measurements 1.3.6.1.4.1.39829.1.3
OBJECT IDENTIFIER    

temperatureFacilityIn 1.3.6.1.4.1.39829.1.3.100
The temperature of the water going into the RackCDU on the Facility side (cold).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER -870..999  

temperatureFacilityOut 1.3.6.1.4.1.39829.1.3.101
The temperature of the water going out of the RackCDU on the Facility side (hot).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER -870..999  

temperatureServerIn 1.3.6.1.4.1.39829.1.3.102
The temperature of the water going into the servers node (cold).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER -870..999  

temperatureServerOut 1.3.6.1.4.1.39829.1.3.103
The temperature of the water going out of the servers node (hot).
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER -870..999  

temperatureAmbient 1.3.6.1.4.1.39829.1.3.104
The temperature of the ambient air close to the RackCDU.
Status: obsolete Access: read-only
OBJECT-TYPE    
  INTEGER -870..999  

pressureServer 1.3.6.1.4.1.39829.1.3.105
The pressure inside the RackCDU on the server side.
Status: mandatory Access: read-only
OBJECT-TYPE    
  Gauge  

pressureFacility 1.3.6.1.4.1.39829.1.3.106
The pressure inside the RackCDU on the facility side.
Status: mandatory Access: read-only
OBJECT-TYPE    
  Gauge  

serverLeak 1.3.6.1.4.1.39829.1.3.107
Boolean indication of whether the RackCDU has detected a leak in the system.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER ok(1), leak(2)  

serverLevel 1.3.6.1.4.1.39829.1.3.108
Boolean indication of whether the RackCDU has detected a low level of cooleant.
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER ok(1), low(2)  

flowFacility 1.3.6.1.4.1.39829.1.3.109
The flow of the cooleant on the facility side.
Status: mandatory Access: read-only
OBJECT-TYPE    
  Gauge  

heatload 1.3.6.1.4.1.39829.1.3.110
The heatload of the cooleant on the facility side. Can be averaged from e.g. 1 to 28800 (24 hours) sec.
Status: mandatory Access: read-only
OBJECT-TYPE    
  Gauge  

controllerOut 1.3.6.1.4.1.39829.1.3.111
The controller output.
Status: mandatory Access: read-only
OBJECT-TYPE    
  Gauge  

network 1.3.6.1.4.1.39829.1.4
OBJECT IDENTIFIER    

ipStoreFlash 1.3.6.1.4.1.39829.1.4.91
store settings to Flash.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER normal(1), store(2)  

modeOfOperation 1.3.6.1.4.1.39829.1.4.92
Mode of operation of ControlBox, can be agent or master.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER agent(1), master(2)  

ipAddr 1.3.6.1.4.1.39829.1.4.93
IP address of ControlBox.
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

priDNS 1.3.6.1.4.1.39829.1.4.94
Primary DNS address of ControlBox.
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

secDNS 1.3.6.1.4.1.39829.1.4.95
Secondary DNS address of ControlBox.
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

netMask 1.3.6.1.4.1.39829.1.4.96
Netmask of ControlBox.
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

gateway 1.3.6.1.4.1.39829.1.4.97
Gateway of ControlBox.
Status: mandatory Access: read-write
OBJECT-TYPE    
  IpAddress  

ipSrc 1.3.6.1.4.1.39829.1.4.98
IP address source of ControlBox, eg. static or dhcp.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER static(1), dhcp(2)  

ipReboot 1.3.6.1.4.1.39829.1.4.99
IP address reboot.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER normal(1), reboot(2)  

controller 1.3.6.1.4.1.39829.1.5
OBJECT IDENTIFIER    

gainProportional 1.3.6.1.4.1.39829.1.5.80
Proportional gain in PID controller.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

gainIntegral 1.3.6.1.4.1.39829.1.5.81
Integral gain in PID controller.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

gainDifferential 1.3.6.1.4.1.39829.1.5.82
Differential gain in PID controller.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

deltaOutMax 1.3.6.1.4.1.39829.1.5.83
Maximum delta output from controller.
Status: mandatory Access: read-write
OBJECT-TYPE    
  Gauge  

limitPwmMax 1.3.6.1.4.1.39829.1.5.84
Maximum PWM output.
Status: mandatory Access: read-write
OBJECT-TYPE    
  Gauge  

limitPwmMin 1.3.6.1.4.1.39829.1.5.85
Minimum PWM output.
Status: mandatory Access: read-write
OBJECT-TYPE    
  Gauge  

setpointFacilityOut 1.3.6.1.4.1.39829.1.5.86
Setpoint for Facility Out Temperature.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..100  

controllerOutAlpha 1.3.6.1.4.1.39829.1.5.87
Controller Out Alpha - damping factor of output.
Status: mandatory Access: read-write
OBJECT-TYPE    
  DisplayString  

units 1.3.6.1.4.1.39829.1.6
OBJECT IDENTIFIER    

fluidHeatCapacity 1.3.6.1.4.1.39829.1.6.70
Heat Capacity of the liquid coolant utilized in the facility loop.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..65000  

heatAverageFactor 1.3.6.1.4.1.39829.1.6.71
The time frame of which the heat load is averaged. A short time frame make the heat load sensative to small changes is temperature and flow which results in a highly fluctuating value. A long time frame stabilizes the value, but also results in a long response time.
Status: mandatory Access: read-write
OBJECT-TYPE    
  Gauge  

harnessVersion 1.3.6.1.4.1.39829.1.6.72
Must be set to the harness version utilized by the RackCDU. The harness version may affect the functionality of the RackCDU and it it therefor important that the versions is matched.
Status: mandatory Access: read-write
OBJECT-TYPE    
  Gauge  

notifications 1.3.6.1.4.1.39829.1.7
OBJECT IDENTIFIER    

snmpTrapsAlarmEnable 1.3.6.1.4.1.39829.1.7.150
Enable SNMP Alarm traps.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

snmpTrapsWarningEnable 1.3.6.1.4.1.39829.1.7.151
Enable SNMP Warning traps.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

smtpTrapsAlarmEnable 1.3.6.1.4.1.39829.1.7.152
Enable SMTP Alarm traps.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

smtpTrapsWarningEnable 1.3.6.1.4.1.39829.1.7.153
Enable SMTP Warning traps.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

warningMinFi 1.3.6.1.4.1.39829.1.7.154
Set Facility In Min Warning level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -75..75  

warningMinEnableFi 1.3.6.1.4.1.39829.1.7.155
Enable Facility In Min Warning level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

warningMaxFi 1.3.6.1.4.1.39829.1.7.156
Set Facility In Max Warning level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -75..75  

warningMaxEnableFi 1.3.6.1.4.1.39829.1.7.157
Enable Facility In Max Warning level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

alarmMinFi 1.3.6.1.4.1.39829.1.7.158
Set Facility In Min Alarm level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -75..75  

alarmMinEnableFi 1.3.6.1.4.1.39829.1.7.159
Enable Facility In Min Alarm level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

alarmMaxFi 1.3.6.1.4.1.39829.1.7.160
Set Facility In Max Alarm level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -75..75  

alarmMaxEnableFi 1.3.6.1.4.1.39829.1.7.161
Enable Facility In Max Alarm level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

warningMinFo 1.3.6.1.4.1.39829.1.7.162
Set Facility Out Min Warning level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -75..75  

warningMinEnableFo 1.3.6.1.4.1.39829.1.7.163
Enable Facility Out Min Warning level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

warningMaxFo 1.3.6.1.4.1.39829.1.7.164
Set Facility Out Max Warning level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -75..75  

warningMaxEnableFo 1.3.6.1.4.1.39829.1.7.165
Enable Facility Out Max Warning level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

alarmMinFo 1.3.6.1.4.1.39829.1.7.166
Set Facility Out Min alarm level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -75..75  

alarmMinEnableFo 1.3.6.1.4.1.39829.1.7.167
Enable Facility Out Min alarm level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

alarmMaxFo 1.3.6.1.4.1.39829.1.7.168
Set Facility Out Max Alarm level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -75..75  

alarmMaxEnableFo 1.3.6.1.4.1.39829.1.7.169
Enable Facility Out Max Alarm level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

warningMinSi 1.3.6.1.4.1.39829.1.7.170
Set Server In Min Warning level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -75..75  

warningMinEnableSi 1.3.6.1.4.1.39829.1.7.171
Enable Server In Min Warning level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

warningMaxSi 1.3.6.1.4.1.39829.1.7.172
Set Server In Max Warning level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -75..75  

warningMaxEnableSi 1.3.6.1.4.1.39829.1.7.173
Enable Server In Max Warning level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

alarmMinSi 1.3.6.1.4.1.39829.1.7.174
Set Server In Min Alarm level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -75..75  

alarmMinEnableSi 1.3.6.1.4.1.39829.1.7.175
Enable Server In Min Alarm level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

alarmMaxSi 1.3.6.1.4.1.39829.1.7.176
Set Server In Max Alarm level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -75..75  

alarmMaxEnableSi 1.3.6.1.4.1.39829.1.7.177
Enable Server In Max Alarm level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

warningMinSo 1.3.6.1.4.1.39829.1.7.178
Set Server Out Min Warning level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -75..75  

warningMinEnableSo 1.3.6.1.4.1.39829.1.7.179
Enable Server Out Min Warning level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

warningMaxSo 1.3.6.1.4.1.39829.1.7.180
Set Server Out Max Warning level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -75..75  

warningMaxEnableSo 1.3.6.1.4.1.39829.1.7.181
Enable Server Out Max Warning level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

alarmMinSo 1.3.6.1.4.1.39829.1.7.182
Set Server Out Min Alarm level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -75..75  

alarmMinEnableSo 1.3.6.1.4.1.39829.1.7.183
Enable Server Out Min Alarm level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

alarmMaxSo 1.3.6.1.4.1.39829.1.7.184
Set Server Out Max Alarm level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER -75..75  

alarmMaxEnableSo 1.3.6.1.4.1.39829.1.7.185
Enable Server Out Max Alarm level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

warningMinFlow 1.3.6.1.4.1.39829.1.7.186
Set Flow Min Warning level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..3500000  

warningMinEnableFlow 1.3.6.1.4.1.39829.1.7.187
Enable Flow Min Warning level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

warningMaxFlow 1.3.6.1.4.1.39829.1.7.188
Set Flow Max Warning level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..3500000  

warningMaxEnableFlow 1.3.6.1.4.1.39829.1.7.189
Enable Flow Max Warning level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

alarmMinFlow 1.3.6.1.4.1.39829.1.7.190
Set Flow Min Alarm level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..3500000  

alarmMinEnableFlow 1.3.6.1.4.1.39829.1.7.191
Enable Flow Min Alarm level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

alarmMaxFlow 1.3.6.1.4.1.39829.1.7.192
Set Flow Max Alarm level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..3500000  

alarmMaxEnableFlow 1.3.6.1.4.1.39829.1.7.193
Enable Flow Max Alarm level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

warningMinPressureServer 1.3.6.1.4.1.39829.1.7.194
Set Server Pressure Min Warning level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..3500  

warningMinEnablePressureServer 1.3.6.1.4.1.39829.1.7.195
Enable Server Pressure Min Warning level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

warningMaxPressureServer 1.3.6.1.4.1.39829.1.7.196
Set Server Pressure Max Warning level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..3500  

warningMaxEnablePressureServer 1.3.6.1.4.1.39829.1.7.197
Enable Server Pressure Max Warning level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

alarmMinPressureServer 1.3.6.1.4.1.39829.1.7.198
Set Server Pressure Min Alarm level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..3500  

alarmMinEnablePressureServer 1.3.6.1.4.1.39829.1.7.199
Enable Server Pressure Min Alarm level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

alarmMaxPressureServer 1.3.6.1.4.1.39829.1.7.200
Set Server Pressure Max Alarm level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..3500  

alarmMaxEnablePressureServer 1.3.6.1.4.1.39829.1.7.201
Enable Server Pressure Max Alarm level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

warningMinPressureFacility 1.3.6.1.4.1.39829.1.7.202
Set Facility Pressure Min Warning level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..3500  

warningMinEnablePressureFacility 1.3.6.1.4.1.39829.1.7.203
Enable Facility Pressure Min Warning level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

warningMaxPressureFacility 1.3.6.1.4.1.39829.1.7.204
Set Facility Pressure Max Warning level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..3500  

warningMaxEnablePressureFacility 1.3.6.1.4.1.39829.1.7.205
Enable Facility Pressure Max Warning level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

alarmMinPressureFacility 1.3.6.1.4.1.39829.1.7.206
Set Facility Pressure Min Alarm level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..3500  

alarmMinEnablePressureFacility 1.3.6.1.4.1.39829.1.7.207
Enable Facility Pressure Min Alarm level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

alarmMaxPressureFacility 1.3.6.1.4.1.39829.1.7.208
Set Facility Pressure Max Alarm level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER 0..3500  

alarmMaxEnablePressureFacility 1.3.6.1.4.1.39829.1.7.209
Enable Facility Pressure Max Alarm level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

alarmEnableLeak 1.3.6.1.4.1.39829.1.7.210
Enable leak detection.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

alarmEnableLevel 1.3.6.1.4.1.39829.1.7.211
Enable low liquid level.
Status: mandatory Access: read-write
OBJECT-TYPE    
  INTEGER disabled(1), enabled(2)  

conformance 1.3.6.1.4.1.39829.1.8
OBJECT IDENTIFIER    

cduProdGroup 1.3.6.1.4.1.39829.1.8.1
OBJECT IDENTIFIER    

cduSetupGroup 1.3.6.1.4.1.39829.1.8.2
OBJECT IDENTIFIER    

cduMeasGroup 1.3.6.1.4.1.39829.1.8.3
OBJECT IDENTIFIER    

cduMeasGroupRev2 1.3.6.1.4.1.39829.1.8.4
OBJECT IDENTIFIER    

cduNetGroup 1.3.6.1.4.1.39829.1.8.5
OBJECT IDENTIFIER    

cduCntlGroup 1.3.6.1.4.1.39829.1.8.6
OBJECT IDENTIFIER    

cduUnitGroup 1.3.6.1.4.1.39829.1.8.7
OBJECT IDENTIFIER    

cduNotifyGroup 1.3.6.1.4.1.39829.1.8.8
OBJECT IDENTIFIER    

cduTrapGroup 1.3.6.1.4.1.39829.1.8.9
OBJECT IDENTIFIER    

cduCompliances 1.3.6.1.4.1.39829.1.8.10
OBJECT IDENTIFIER    

cduEventGroup 1.3.6.1.4.1.39829.1.8.11
OBJECT IDENTIFIER    

cduTrapGroupRev2 1.3.6.1.4.1.39829.1.8.12
OBJECT IDENTIFIER    

cduCompliancesRev2 1.3.6.1.4.1.39829.1.8.13
OBJECT IDENTIFIER    

eventDescriptors 1.3.6.1.4.1.39829.1.9
OBJECT IDENTIFIER    

eventDescription 1.3.6.1.4.1.39829.1.9.1
Text which provide the user with a corrective action in case of a warning or alarm trap. IMPORTANT: Must only be used in traps! Any other use of this object is invalid.
Status: mandatory Access: read-only
OBJECT-TYPE    
  DisplayString  

eventValue 1.3.6.1.4.1.39829.1.9.2
Event value placeholder sent with generic traps where the unit of the value can be different. IMPORTANT: Must only be used in traps! Any other use of this object is invalid
Status: mandatory Access: read-only
OBJECT-TYPE    
  INTEGER  

alarmNotify 500
Trap alarm notification information for the SNMP Manager (obsolete).
TRAP-TYPE    

warningNotify 501
Trap warning notification information for the SNMP Manager (obsolete).
TRAP-TYPE    

facilitySupplyWarning 504
Facility supply temperature warning.
TRAP-TYPE    

facilityReturnWarning 505
Facility return temperature warning.
TRAP-TYPE    

serverSupplyWarning 506
Server supply temperature warning.
TRAP-TYPE    

serverReturnWarning 507
Server return temperature warning.
TRAP-TYPE    

facilityPressureWarning 508
Facility pressure warning.
TRAP-TYPE    

serverPressureWarning 509
Server pressure warning.
TRAP-TYPE    

facilityFlowWarning 512
Facility flow warning.
TRAP-TYPE    

facilitySupplyAlarm 517
Facility supply temperature alarm.
TRAP-TYPE    

facilityReturnAlarm 518
Facility return temperature alarm.
TRAP-TYPE    

serverSupplyAlarm 519
Server supply temperature alarm.
TRAP-TYPE    

serverReturnAlarm 520
Server return temperature alarm.
TRAP-TYPE    

facilityPressureAlarm 521
Facility pressure alarm.
TRAP-TYPE    

serverPressureAlarm 522
Server pressure alarm.
TRAP-TYPE    

leakDetectionAlarm 523
Leak detection alarm.
TRAP-TYPE    

liquidLevelAlarm 524
Low liquid level alarm.
TRAP-TYPE    

facilityFlowAlarm 525
Facility flow alarm.
TRAP-TYPE