APNL-MODULAR-PDU-MIB

File: APNL-MODULAR-PDU-MIB.mib (25758 bytes)

Imported modules

SNMPv2-SMI SNMPv2-TC

Imported symbols

NOTIFICATION-TYPE OBJECT-TYPE MODULE-IDENTITY
enterprises IpAddress Unsigned32
Integer32 DateAndTime DisplayString

Defined Types

NodeEntry  
SEQUENCE    
  nodeIndex Unsigned32
  nodeType INTEGER
  nodeOutlet Unsigned32
  nodeAlarmStatus BITS
  nodePower Unsigned32
  nodeAcurrent Unsigned32
  nodePeakCurrent Unsigned32
  nodeVoltage Unsigned32
  nodeMinVoltage Unsigned32
  nodeKvar Unsigned32
  nodeFrequency Unsigned32
  nodePowerFactor Unsigned32
  nodeSwitchOperStatus INTEGER
  nodeSwitchAdminStatus INTEGER
  nodeCurrHiThresh Unsigned32
  nodeCurrLoThresh Unsigned32
  nodeVoltHiThresh Unsigned32
  nodeVoltLoThresh Unsigned32
  nodeAlarmSelector BITS
  nodeName DisplayString
  nodePhase INTEGER

SensorEntry  
SEQUENCE    
  sensorIndex Unsigned32
  sensorType INTEGER
  sensorAlarmStatus BITS
  sensorValue Integer32
  sensorSwitchOperStatus INTEGER
  sensorSwitchAdminStatus INTEGER
  sensorHiThresh Integer32
  sensorLoThresh Integer32
  sensorAlarmSelector BITS
  sensorName DisplayString

Defined Values

apNederland 1.3.6.1.4.1.29640
This MIB module defines the modular PDU version of AP Nederland.
MODULE-IDENTITY    

apnlDirectory 1.3.6.1.4.1.29640.1
OBJECT IDENTIFIER    

apnlMib 1.3.6.1.4.1.29640.2
OBJECT IDENTIFIER    

apnlTmp 1.3.6.1.4.1.29640.3
OBJECT IDENTIFIER    

apnlModules 1.3.6.1.4.1.29640.4
OBJECT IDENTIFIER    

cm 1.3.6.1.4.1.29640.4.1
OBJECT IDENTIFIER    

cmTraps 1.3.6.1.4.1.29640.4.2
OBJECT IDENTIFIER    

pdu 1.3.6.1.4.1.29640.4.3
OBJECT IDENTIFIER    

pduTraps 1.3.6.1.4.1.29640.4.4
OBJECT IDENTIFIER    

apnlTest 1.3.6.1.4.1.29640.5
OBJECT IDENTIFIER    

apnlDemo 1.3.6.1.4.1.29640.6
OBJECT IDENTIFIER    

apnlMIBConformance 1.3.6.1.4.1.29640.7
OBJECT IDENTIFIER    

pduType 1.3.6.1.4.1.29640.4.3.1
Type of the Pdu. PduModular (0) Modulaire OEC2 PDU communication through SNMPV3, MOD-BUS or AP-BUS in emulation mode. PduGateway1 (1) Gateway to connect OEC1 products with external AP-BUS protocol to OEC2 Manager (SNMPV3). PduGateway2 (2) Gateway to connect OEC2 products with external MOD-BUS to OEC Manager (SNMPV3).
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER pduModular(0), pduGateway1(1), pduGateway2(2)  

pduProductIdentifier 1.3.6.1.4.1.29640.4.3.2
Unique serial number to identify a pdu, the number is between 1 and 65535.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pduSerialNumber 1.3.6.1.4.1.29640.4.3.3
PDU onboard Serial Number.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(1..16)  

pduStatus 1.3.6.1.4.1.29640.4.3.4
Status of the Pdu. pduBusy (0) Indicates that an admin command is in progress. pduReady (1) The execution of an admin command was successfull. pduAlarm (2) This state is not in use. pduError (3) The execution of an admin command failed.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER pduBusy(0), pduReady1(1), pduAlarm(2), pduError(3)  

pduPower 1.3.6.1.4.1.29640.4.3.5
The total measured pdu power in Kilo Watt's*Hour.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

pduPowerL1 1.3.6.1.4.1.29640.4.3.6
The total measured pdu power in Kilo Watt's*Hour for phase 1.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

pduPowerL2 1.3.6.1.4.1.29640.4.3.7
The total measured pdu power in Kilo Watt's*Hour for phase 2.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

pduPowerL3 1.3.6.1.4.1.29640.4.3.8
The total measured pdu power in Kilo Watt's*Hour for phase 3.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

pduKvar 1.3.6.1.4.1.29640.4.3.9
The total Reactive Power of the pdu. It is the power that magnetic equipment (transformer, motor and relay) needs to produce the magnetizing flux.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

pduKvarL1 1.3.6.1.4.1.29640.4.3.10
The total Reactive Power of the pdu for phase 1. It is the power that magnetic equipment (transformer, motor and relay) needs to produce the magnetizing flux.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

pduKvarL2 1.3.6.1.4.1.29640.4.3.11
The total Reactive Power of the pdu for phase 2. It is the power that magnetic equipment (transformer, motor and relay) needs to produce the magnetizing flux.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

pduKvarL3 1.3.6.1.4.1.29640.4.3.12
The total Reactive Power of the pdu for phase 3. It is the power that magnetic equipment (transformer, motor and relay) needs to produce the magnetizing flux.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

pdulAcurrent 1.3.6.1.4.1.29640.4.3.13
The total measured ac current for the pdu (in 1/10th Amperes) .
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

pduAcurrentL1 1.3.6.1.4.1.29640.4.3.14
The total measured ac current for phase 1 (in 1/10th Amperes).
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

pduAcurrentL2 1.3.6.1.4.1.29640.4.3.15
The total measured ac current for phase 2 (in 1/10th Amperes).
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

pduAcurrentL3 1.3.6.1.4.1.29640.4.3.16
The total measured ac current for phase 3 (in 1/10th Amperes).
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

pduCurIpAddress 1.3.6.1.4.1.29640.4.3.17
The current PDU IPv4 Address by which TCP/IP access is available.
Status: current Access: read-only
OBJECT-TYPE    
  IpAddress  

pduCurSubNetMask 1.3.6.1.4.1.29640.4.3.18
The current PDU IPv4 Subnet Mask used by the Ipstack (e.g: 255.255.255.0).
Status: current Access: read-only
OBJECT-TYPE    
  IpAddress  

pduCurDefGwAddress 1.3.6.1.4.1.29640.4.3.19
The current PDU IPv4 default gateway address used by the Ipstack (e.g: 192.168.1.1).
Status: current Access: read-only
OBJECT-TYPE    
  IpAddress  

pduNumberOfNodes 1.3.6.1.4.1.29640.4.3.20
Number of items in the node table.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pduNumberOfSensors 1.3.6.1.4.1.29640.4.3.21
Number of items in the sensor table.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

pduSoftwareVersion 1.3.6.1.4.1.29640.4.3.22
PDU software version number.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(1..10)  

pduFirmwareVersion 1.3.6.1.4.1.29640.4.3.23
PDU firmware version number.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(1..10)  

pduBusProtocol 1.3.6.1.4.1.29640.4.3.24
Selected protocol used on the external bus of the pdu. AP-BUS (0) Protocol used by OEC1 products or by OEC2 products in emulation mode. MOD-BUS (1) Protocol used by OEC2 products.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER apbus(0), modbus(1)  

pduAdminCommand 1.3.6.1.4.1.29640.4.3.25
PDU admin management Commands: noOp (0) No operation. rebootPdu (1) Reboot the PDU (to execute new settings). rediscover (2) Not supported. updateSofware (3) Not supported. resetConfig (4) Node and group tables will be cleared . resetSNMPv3Config (5) Not supported. resetNetworkSetting (6) Reset network params: ip address, defualt gatewy, subnet mask. readDataFromBusPdu (7) Read data from a PDU connected to the external bus (address is set in pduBusAddress). writeDataToBusPdu (8) With this command modified data is writen back to the bus PDU (address is set in pduBusAddress).
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER noOp(0), rebootPdu(1), rediscover(2), updateSofware(3), resetConfig(4), resetSNMPv3Config(5), resetNetworkSetting(6), readDataFromBusPdu(7), writeDataToBusPdu(8)  

pduStartupIpAddress 1.3.6.1.4.1.29640.4.3.26
Not supported.
Status: current Access: read-write
OBJECT-TYPE    
  IpAddress  

pduStartupSubNetMask 1.3.6.1.4.1.29640.4.3.27
Not supported.
Status: current Access: read-write
OBJECT-TYPE    
  IpAddress  

pduStartupDefGwAddress 1.3.6.1.4.1.29640.4.3.28
Not supported.
Status: current Access: read-write
OBJECT-TYPE    
  IpAddress  

pduRealTimeClock 1.3.6.1.4.1.29640.4.3.29
PDU Real-Time Clock. Maybe set by the manager.
Status: current Access: read-write
OBJECT-TYPE    
  DateAndTime  

pduEnableFeatures 1.3.6.1.4.1.29640.4.3.30
Array of bits each one an specific feature within the pdu: globalWebEnabled (0) This bit enables the PDU webpages. globalUsbEnabled (1) This bit enables the USB menu. globalSwitchEnabled (2) This bit enables switching in general. displaySwitchEnabled (3) This bit enables switching through the presentation module. webSwitchEnabled (4) This bit enables switching throuhg the web inteface.
Status: current Access: read-write
OBJECT-TYPE    
  BITS globalWebEnabled(0), globalUsbEnabled(1), globalSwitchEnabled(2), displaySwitchEnabled(3), webSwitchEnabled(4)  

pduBusAddress 1.3.6.1.4.1.29640.4.3.31
Address used to access this PDU via the external bus. When MOD-BUS protocol is used the address is valid between 1-247. When AP-BUS protocol is used the address is valid between 1-65535.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

pduName 1.3.6.1.4.1.29640.4.3.32
Name of the PDU.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(1..32)  

nodeTable 1.3.6.1.4.1.29640.4.3.33
A table of the modules on the PDU. Each entry represents an module unit.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    NodeEntry

nodeEntry 1.3.6.1.4.1.29640.4.3.33.1
An port entry in the port table.
Status: current Access: not-accessible
OBJECT-TYPE    
  NodeEntry  

nodeIndex 1.3.6.1.4.1.29640.4.3.33.1.1
The node table Index.
Status: current Access: not-accessible
OBJECT-TYPE    
  Unsigned32 1..30  

nodeType 1.3.6.1.4.1.29640.4.3.33.1.2
Type of the node. TypeUnknown (0) Unknown node. TypePresModChar (1) PM LCD Character Module. TypePresModMono (2) PM Mono Graphics Module. TypePresModGraph (3) PM Color Graphics Module. TypePowerMeter (4) Power meter. TypePowerMeterSwitch (5) Switchable power meter. TypeSwitch (6) Switch only.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER typeUnknown(0), typePresModChar(1), typePresModMono(2), typePresModGraph(3), typePowerMeter(4), typePowerMeterSwitch(5), typeSwitch(6)  

nodeOutlet 1.3.6.1.4.1.29640.4.3.33.1.3
The number associated with the physical outlet of the node. The special value of 0 indicates that this entry is not associated with a physical port.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

nodeAlarmStatus 1.3.6.1.4.1.29640.4.3.33.1.4
Array of bits each one indicates an alarm activated in the alarm selector value. TrapCurrHi (0) The current is to high against the high current threshold. TrapCurrLo (1) The current is to low against the low current threshold. TrapVoltHi (2) The voltage is to high against the high voltage threshold. TrapVoltLo (3) The volage is to low against the low voltage threshold. SwitchOn (4) The switch is on against the switch on bitfield. SwitchOff (5) The switch is off against the switch off bitfield.
Status: current Access: read-only
OBJECT-TYPE    
  BITS trapCurrHi(0), trapCurrLo(1), trapVoltHi(2), trapVoltLo(3), switchOn(4), switchOff(5)  

nodePower 1.3.6.1.4.1.29640.4.3.33.1.5
The measured node power in Kilo Watt's*Hour.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

nodeAcurrent 1.3.6.1.4.1.29640.4.3.33.1.6
The measured ac current at the node (in 1/10th Amperes).
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

nodePeakCurrent 1.3.6.1.4.1.29640.4.3.33.1.7
The measured max current since last reset of the node (in 1/10th Amperes).
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

nodeVoltage 1.3.6.1.4.1.29640.4.3.33.1.8
The measured voltage on the node.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

nodeMinVoltage 1.3.6.1.4.1.29640.4.3.33.1.9
The measured minimum voltage at the node since last reset.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

nodeKvar 1.3.6.1.4.1.29640.4.3.33.1.10
The Reactive Power. It is the power that magnetic equipment (transformer, motor and relay) needs to produce the magnetizing flux.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

nodeFrequency 1.3.6.1.4.1.29640.4.3.33.1.11
The frequency of alternating current in Hertz. e.g 50 in Europe or 60 in USA.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

nodePowerFactor 1.3.6.1.4.1.29640.4.3.33.1.12
The effective power facton (Cosinus Phi) in percents of the node.
Status: current Access: read-only
OBJECT-TYPE    
  Unsigned32  

nodeSwitchOperStatus 1.3.6.1.4.1.29640.4.3.33.1.13
The actual operational Status of the node. Unknown (0) not known status. Off (1) switch is off. On (2) switch is on.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER unknown(0), off(1), on(2)  

nodeSwitchAdminStatus 1.3.6.1.4.1.29640.4.3.33.1.14
The desired admin Status of the switch. Unknown (0) not known. Off (1) switch is off. On (2) switch is on.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER unknown(0), off(1), on(2)  

nodeCurrHiThresh 1.3.6.1.4.1.29640.4.3.33.1.15
The current high threshold (in 1/10th Amperes).
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

nodeCurrLoThresh 1.3.6.1.4.1.29640.4.3.33.1.16
The current low threshold (in 1/10th Amperes).
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

nodeVoltHiThresh 1.3.6.1.4.1.29640.4.3.33.1.17
The voltage high threshold.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

nodeVoltLoThresh 1.3.6.1.4.1.29640.4.3.33.1.18
The voltage low threshold.
Status: current Access: read-write
OBJECT-TYPE    
  Unsigned32  

nodeAlarmSelector 1.3.6.1.4.1.29640.4.3.33.1.19
Array of bits each one controls one alarm. TrapCurrHi (0) Enable/disable the high current alarm. TrapCurrLo (1) Enable/disable the low current alarm. TrapVoltHi (2) Enable/disable the high voltage alarm. TrapVoltLo (3) Enable/disable the low voltage alarm. SwitchOn (4) Enable/disable the specific switch on alarm. SwitchOff (5) Enable/disable the specific switch off alarm.
Status: current Access: read-write
OBJECT-TYPE    
  BITS trapCurrHi(0), trapCurrLo(1), trapVoltHi(2), trapVoltLo(3), switchOn(4), switchOff(5)  

nodeName 1.3.6.1.4.1.29640.4.3.33.1.20
The node name. My be set by manager.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(1..14)  

nodePhase 1.3.6.1.4.1.29640.4.3.33.1.21
The measured phase of the node. Maybe assigned when not configured in production. PhaseUnknown (0). PhaseL1 (1). PhaseL2 (2). PhaseL3 (3).
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER phaseUnknown(0), phaseL1(1), phaseL2(2), phaseL3(3)  

sensorTable 1.3.6.1.4.1.29640.4.3.34
A table of the Sensors on the PDU. Each entry represents an an Sensor unit.
Status: current Access: not-accessible
OBJECT-TYPE    
  SEQUENCE OF  
    SensorEntry

sensorEntry 1.3.6.1.4.1.29640.4.3.34.1
An Sensor Entry in the Sensor table
Status: current Access: not-accessible
OBJECT-TYPE    
  SensorEntry  

sensorIndex 1.3.6.1.4.1.29640.4.3.34.1.1
The Sensor table Index.
Status: current Access: not-accessible
OBJECT-TYPE    
  Unsigned32 1..4  

sensorType 1.3.6.1.4.1.29640.4.3.34.1.2
Sensor Typ: Measured values are used according to sensor type. Other (0) unknown sensor type. Temperature (1) . Humidity (2). Smoke (3). CO1 (4). Vibration (5). Doorstatus (6).
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER other(0), temperature(1), humidity(2), smoke(3), co1(4), vibration(5), doorStatus(6)  

sensorAlarmStatus 1.3.6.1.4.1.29640.4.3.34.1.3
Array of bits each one indicates an alarm activated in the alarm selector value.
Status: current Access: read-only
OBJECT-TYPE    
  BITS trapHi(0), trapLo(1), switchOn(2), switchOff(3), beeperHi(4), beeperLo(5)  

sensorValue 1.3.6.1.4.1.29640.4.3.34.1.4
The measured value of the sensor, units are depending on sensor type.
Status: current Access: read-only
OBJECT-TYPE    
  Integer32  

sensorSwitchOperStatus 1.3.6.1.4.1.29640.4.3.34.1.5
The actual operational Status of the switch.
Status: current Access: read-only
OBJECT-TYPE    
  INTEGER unknown(0), off(1), on(2)  

sensorSwitchAdminStatus 1.3.6.1.4.1.29640.4.3.34.1.6
The desired admin Status of the switch.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER unknown(0), off(1), on(2)  

sensorHiThresh 1.3.6.1.4.1.29640.4.3.34.1.7
High threshold.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

sensorLoThresh 1.3.6.1.4.1.29640.4.3.34.1.8
Low threshold.
Status: current Access: read-write
OBJECT-TYPE    
  Integer32  

sensorAlarmSelector 1.3.6.1.4.1.29640.4.3.34.1.9
Array of bits each one controls one alarm. E.g trap, beeper etc.
Status: current Access: read-write
OBJECT-TYPE    
  BITS trapHi(0), trapLo(1), switchOn(2), switchOff(3), beeperHi(4), beeperLo(5)  

sensorName 1.3.6.1.4.1.29640.4.3.34.1.10
The sensor name. May be set by the manager.
Status: current Access: read-write
OBJECT-TYPE    
  DisplayString Size(1..12)  

trapType 1.3.6.1.4.1.29640.4.4.1
An enumation value to indicate an Alarm trap: pduPduAlarm.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  INTEGER voltageHiAlarm(0), voltageLoAlarm(1), currentHiAlarm(2), currentLoAlarm(3), tempHiAlarm(4), tempLoAlarm(5), humidityHiAlarm(6), humidityLoAlarm(7), switchOnAlarm(8), switchOffAlarm(9), powerHiAlarm(10), blackBoxColdTrap(11)  

pduTableType 1.3.6.1.4.1.29640.4.4.2
The table type.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  INTEGER pduNodeTable(0), pduSensorTable(1)  

trapTableIndex 1.3.6.1.4.1.29640.4.4.3
The index of the table entry for which the trap is issued.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Integer32  

trapThreshHoldType 1.3.6.1.4.1.29640.4.4.4
The threshold type for which the trap is made.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  INTEGER trapThresholdOther(0), trapThresholdHi(1), trapThresholdLo(2)  

trapThreshHold 1.3.6.1.4.1.29640.4.4.5
The threshold reference value.
Status: current Access: accessible-for-notify
OBJECT-TYPE    
  Integer32  

pduVoltageAlarm 1.3.6.1.4.1.29640.4.4.6
Voltage alarm.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

pduCurrentAlarm 1.3.6.1.4.1.29640.4.4.7
Current alaram.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

pduPowerAlarm 1.3.6.1.4.1.29640.4.4.8
Power alarm.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

sensorAlarm 1.3.6.1.4.1.29640.4.4.9
Sensor Alarm: Temperature, Humidity or another type. The sensorType indicates the type of alarm. The sensorValue indicate the measured value.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE    

pduSwitchAlarm 1.3.6.1.4.1.29640.4.4.10
Not supported.
Status: current Access: accessible-for-notify
NOTIFICATION-TYPE