ADH-NETCOM-MIB

File: ADH-NETCOM-MIB.mib (7014 bytes)

Imported modules

SNMPv2-SMI SNMPv2-TC

Imported symbols

MODULE-IDENTITY OBJECT-IDENTITY OBJECT-TYPE
Integer32 enterprises DisplayString

Defined Values

environmentalTechnology 1.3.6.1.4.1.32185
The Structure of Management Information for Environmental Technology Inc. SNMP devices
MODULE-IDENTITY    

netcom 1.3.6.1.4.1.32185.2
ADH NETCOM
Status: current Access: read-write
OBJECT-IDENTITY    

statusInfo 1.3.6.1.4.1.32185.2.1
OBJECT IDENTIFIER    

paramsInfo 1.3.6.1.4.1.32185.2.2
OBJECT IDENTIFIER    

allStatuses 1.3.6.1.4.1.32185.2.1.1
Summary: same as objects 2-7, separated by semicolons
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(80)  

pressurePSI 1.3.6.1.4.1.32185.2.1.2
Pressure, in PSI or mbar
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(10)  

dutycycle 1.3.6.1.4.1.32185.2.1.3
Current duty cycle, in percent; --- if none available
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(10)  

statusVars 1.3.6.1.4.1.32185.2.1.4
Summary of the status of the unit. Is always 7 characters Character 1 is super-state: govering whole system, if this unit is a master S=slave (not a master) M=master; N=master but system off line D=director; D=director but system off line master: for redundant systems director: for increasing pumping capability Character 2 is major state: N=normal, S=standby, L=leaky Character 3 is environment: N=normal, C=cold, H=hot Character 4 is canister 1 condition: O=OK (ie dry), F=full (wet), U=unknown, D=dead Character 5 is canister 1 usage: I=idle, U=in use, R=regenerating Character 6 is canister 2 condition, as in character 4 Character 7 is canister 2 usage, as in character 5
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(6)  

temperature 1.3.6.1.4.1.32185.2.1.5
Current temperature, in degrees F or C
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(10)  

alarms 1.3.6.1.4.1.32185.2.1.6
Current alarm conditions: is a list of them Each character has a - for no alarm, or an A or W if there is an alarm. A means alarm (serious), W means a warning (not so serious). Severity levels may later change. List of alarms: (later versions may add more): A1: Low pressure A2: High pressure W3: High duty cycle W4: High temperature W5: Low temperature W6: Unused A7: Canister 1 won't heat A8: Canister 1 won't cool A9: Canister 2 won't heat A10: Canister 2 won't cool A11: Unable to pressurize A12: Dew point alarm W13: Compressor timeout (for future use) W14: Communications error A15: Canister 1 thermistor bad A16: Canister 2 thermistor bad A17: Ambient thermistor bad A18: Overpressure A19: Bad calibrations in EEPROM A20: Bad limits in EEPROM A21: Short cycling A22: Pump shut down due to error condition
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(30)  

compressorHours 1.3.6.1.4.1.32185.2.1.7
Number of hours that the compressor has been running; resolution is tenths of an hour.
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(30)  

majorState 1.3.6.1.4.1.32185.2.1.8
Major state of the dehydrator. Online: currently pressurizing. Standby: not pressurizing. Leaky: shut down because of inability to pressurize.
Status: current Access: read-write
OBJECT-TYPE    
  INTEGER online(1), standby(2), leaky(3)  

cycleTime 1.3.6.1.4.1.32185.2.1.9
Time of last duty cycle in seconds; 0.0 means none available
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(10)  

lowerLimit 1.3.6.1.4.1.32185.2.2.1
The pressure, in PSI or mbar, at which the unit starts to pump
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(10)  

upperLimit 1.3.6.1.4.1.32185.2.2.2
The pressure, in PSI or mbar, which the unit pressurizes to
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(10)  

lowerAlarmLimit 1.3.6.1.4.1.32185.2.2.3
The pressure, in PSI or mbar, below which the unit declares a low pressure alarm
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(10)  

upperAlarmLimit 1.3.6.1.4.1.32185.2.2.4
The pressure, in PSI or mbar, above which the unit declares a high pressure alarm
Status: current Access: read-only
OBJECT-TYPE    
  DisplayString Size(10)